{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F68325","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F68325","canonicalUrl":"https://aoctrl.com/schneider/A9F68325","factsUrl":"https://aoctrl.com/api/mcp/products/A9F68325","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iT60, A9F68325, miniature circuit breaker, 25 A, C curve, 3 poles, 54 mm width, DIN rail mount.","salesMarkdown":"The Schneider Electric A9F68325 is a 3-pole Acti9 iT60 miniature circuit breaker rated at 25 A with a C curve, built for distribution boards on DIN rail. The A9F68325 delivers 36 kA Icu at 12–133 V AC, 20 kA Icu at 220–240 V AC, and 10 kA Icu at 380–415 V AC per IEC 60947-2. That 20 kA at 240 V is the number most panel builders care about for a 25 A C-curve MCB in a North American or European distribution board — it means this breaker can safely interrupt a 20,000 A fault without welding its contacts or bursting the case. At 400 V, the Icn per IEC 60898-1 is 10 kA, which covers the standard domestic/commercial fault level. The utilisation category is A, so it's not intended for motor switching under load — use a contactor for that. ## What the C curve and thermal-magnetic trip mean on the route The thermal-magnetic trip unit handles overloads (thermal bimetal) and short-circuits (solenoid) in one package. Magnetic tripping limit is 8 x In, so at 25 A that's 200 A instantaneous trip — fast enough to protect wiring but tolerant of the inrush from a small motor or a bank of contactor coils. The thermal element is tropicalised to class 2 per EN/IEC 60068-2-78, meaning it holds up in high-humidity environments without nuisance tripping from corrosion on the bimetal. Snaps onto DIN rail, 54 mm wide (6 x 9 mm pitches). Terminals accept 1–25 mm² rigid or 1–16 mm² flexible copper, with a tightening torque of 2 N·m. The removable comb busbar is installed from the factory — you can daisy-chain the line side across multiple breakers without extra wiring. Pollution degree 3 per IEC 60947-2, meaning it's rated for conductive dust and condensation typical in industrial enclosures.","metaTitle":"Schneider Electric A9F68325 Acti9 iT60 MCB, 25 A, C Curve, 3","metaDescription":"Schneider Electric A9F68325 Acti9 iT60 miniature circuit breaker, 25 A rated current, C curve, 3 poles, 36 kA breaking capacity at 133 V AC. Current production. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Range":"Acti9","Width":"54 mm","Colour":"White","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"C","9 Mm Pitches":"6","Control type":"Toggle","Network type":"AC/DC","Product name":"Acti9 iT60","Mounting mode":"Removable comb busbar installed","Tropicalisation":"2 conforming to EN/IEC 60068-2-78","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iT60N","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"95 %","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","Operating altitude":"0...2000 m","[In] rated current":"25 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Single terminal (top or bottom) 1...25 mm² rigid Single terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 B conforming to IEC 60529","Magnetic tripping limit":"8 x In +/- 20 %","Earth-leakage protection":"Without","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 180 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/be/en/product/A9F68325/miniature-circuit-breaker-mcb-acti9-it60n-3p-25a-c-curve-6000a-iec-en-608981-10ka-iec-en-609472/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F68325/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9F68325 and get a price?","answer":"This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What standards does the A9F68325 comply with?","answer":"It is dual-certified to EN/IEC 60947-2 (industrial) and EN/IEC 60898-1 (domestic/commercial), with suitability for isolation per both standards. Pollution degree 3, overvoltage category IV, and tropicalisation class 2 per EN/IEC 60068-2-78."},{"question":"What is the breaking capacity of A9F68325 at 240 V?","answer":"The breaking capacity is 20 kA Icu at 220–240 V AC per IEC 60947-2, and 10 kA Icn at 400 V per IEC 60898-1."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F68325","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F68325 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}