{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F68401","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F68401","canonicalUrl":"https://aoctrl.com/schneider/A9F68401","factsUrl":"https://aoctrl.com/api/mcp/products/A9F68401","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iT60 miniature circuit breaker, A9F68401, 1 A rated current, C-curve, 4 poles, 50 kA breaking capacity at 415 V AC, DIN rail mount.","salesMarkdown":"The Schneider Electric A9F68401 is a 4-pole miniature circuit breaker from the Acti9 iT60 range, rated 1 A with a C-curve trip characteristic. The magnetic trip fires at 8 x In ±20 %. Terminals accept 1–25 mm² rigid or 1–16 mm² flexible, with a 2 N·m tightening torque. The removable comb busbar makes daisy-chaining multiple poles straightforward in a distribution board. Dual-rated to EN/IEC 60947-2 (industrial) and EN/IEC 60898-1 (household). That means it passes both the industrial breaking-capacity test (50 kA Icu at 415 V) and the domestic Icn test (6 kA at 400 V). Suitability for isolation is confirmed under both standards, so you can use it as a disconnecting means.","metaTitle":"Schneider A9F68401 Acti9 iT60 MCB, 1A C-Curve 4P 50kA","metaDescription":"Schneider Electric A9F68401 Acti9 iT60 miniature circuit breaker, 1 A rated, C-curve, 4 poles, 50 kA breaking capacity at 415 V AC. Complies with EN/IEC 60947-2 and 60898-1. Active","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Range":"Acti9","Width":"72 mm","Colour":"White","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"C","9 Mm Pitches":"8","Control type":"Toggle","Network type":"AC DC","Product name":"Acti9 iT60","Mounting mode":"Removable comb busbar installed","Tropicalisation":"2 conforming to EN/IEC 60068-2-78","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"50 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iT60N","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"95 %","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","Operating altitude":"0...2000 m","[In] rated current":"1 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Single terminal (top or bottom) 1...25 mm² rigid Single terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 B conforming to IEC 60529","Magnetic tripping limit":"8 x In +/- 20 %","Earth-leakage protection":"Without","Number of protected poles":"4","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"50 kA 100 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 25 kA 100 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 250 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a896acd5659ee6880544d8d3317bae83.pdf","sourceUrl":"https://www.se.com/be/en/product/A9F68401/it60n-miniature-circuit-breaker-4p-1-a-c-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F68401/alternatives.json"},"ai":{"faq":[{"question":"What is A9F68401's listed range?","answer":"The A9F68401 belongs to the Schneider Electric Acti9 range, specifically the iT60 series."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F68401","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F68401 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}