{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F68410","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F68410","canonicalUrl":"https://aoctrl.com/schneider/A9F68410","factsUrl":"https://aoctrl.com/api/mcp/products/A9F68410","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iT60, A9F68410, miniature circuit breaker, 10 A rated current, C-curve, 4 poles, 72 mm width, DIN rail mount.","salesMarkdown":"The Schneider Electric A9F68410 is an Acti9 iT60 miniature circuit breaker rated at 10 A with a C-curve magnetic trip characteristic, 4 poles, and a 72 mm width for DIN-rail mounting in distribution panels. The breaking capacity table is the main thing to check against your fault study. At 220…240 V AC this breaker interrupts 20 kA Icu per EN/IEC 60947-2, and at 380…415 V AC it holds 10 kA Icu. The IEC 60898-1 rating is 10 kA Icn at 400 V AC. If your calculated fault level sits above 10 kA at 400 V, this breaker still coordinates because the 60947-2 Icu at that voltage is the same 10 kA — no hidden gap. The 36 kA Icu at 12…133 V AC is a low-voltage edge case for control transformers or battery-backed DC buses. ## Trip curve and coordination C-curve means the magnetic trip fires at 8 x In ±20 %, so for this 10 A breaker the instantaneous trip threshold sits between 64 A and 96 A. That suits general-purpose distribution loads — lighting, small motor starters, control transformers — where the inrush is moderate but not as high as a motor-starting D-curve would handle. The limitation class is 3 per EN/IEC 60898-1, meaning it limits let-through energy enough to protect downstream wiring under short-circuit conditions without cascading the trip upstream. Thermal-magnetic trip unit, no earth-leakage module built in. Snaps onto DIN rail, 72 mm wide (8 x 9 mm pitches). The removable comb busbar is installed from the factory, so you can daisy-chain phases across adjacent breakers without extra wiring. Terminals accept 1…25 mm² rigid or 1…16 mm² flexible on top or bottom; strip length 14 mm, torque to 2 N·m.","metaTitle":"Schneider Electric A9F68410 Acti9 iT60 MCB, 10 A C-Curve 4P","metaDescription":"Schneider Electric A9F68410 Acti9 iT60 miniature circuit breaker, 10 A, C-curve, 4-pole, 36 kA breaking capacity, dual-standard EN/IEC 60947-2 & 60898-1. Current production, availa","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Range":"Acti9","Width":"72 mm","Colour":"White","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"C","9 Mm Pitches":"8","Control type":"Toggle","Network type":"AC/DC","Product name":"Acti9 iT60","Mounting mode":"Removable comb busbar installed","Tropicalisation":"2 conforming to EN/IEC 60068-2-78","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iT60N","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"95 %","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","Operating altitude":"0...2000 m","[In] rated current":"10 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Single terminal (top or bottom) 1...25 mm² rigid Single terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 B conforming to IEC 60529","Magnetic tripping limit":"8 x In +/- 20 %","Earth-leakage protection":"Without","Number of protected poles":"4","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 250 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/be/en/product/A9F68410/miniature-circuit-breaker-mcb-acti9-it60n-4p-10a-c-curve-6000a-iec-en-608981-10ka-iec-en-609472/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F68410/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of the A9F68410 at 400 V AC?","answer":"At 380…415 V AC the breaking capacity is 10 kA Icu per EN/IEC 60947-2, and the IEC 60898-1 rating is 10 kA Icn at 400 V AC."},{"question":"What standards does the A9F68410 comply with?","answer":"It is certified to both EN/IEC 60947-2 and EN/IEC 60898-1, covering industrial feeder and branch-circuit overcurrent protection."},{"question":"How do I get pricing and availability for the A9F68410?","answer":"Submit an RFQ through this listing; availability and current pricing are confirmed at quote time through independent distribution channels."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F68410","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F68410 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}