{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F68463","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F68463","canonicalUrl":"https://aoctrl.com/schneider/A9F68463","factsUrl":"https://aoctrl.com/api/mcp/products/A9F68463","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iT60, A9F68463, miniature circuit breaker, 63 A, C curve, 4 poles, 36 kA breaking capacity, DIN rail mount.","salesMarkdown":"The Schneider Electric A9F68463 is an Acti9 iT60 miniature circuit breaker rated 63 A with a C curve, 4 poles, and a thermal-magnetic trip unit. The 63 A continuous rating and 4-pole format make this a main or feeder breaker for three-phase distribution panels, not a branch device for small loads. At 12–133 V AC it interrupts 36 kA Icu; at 220–240 V AC that drops to 20 kA; at 380–415 V AC it's 10 kA; and at 440 V AC it's 6 kA — all per IEC 60947-2. That's a high-interrupting rating for a 72 mm wide, 4-pole MCB — it handles industrial fault levels where a standard 6 kA or 10 kA breaker would need an upstream current-limiting fuse or a larger frame. Snaps onto DIN rail, 72 mm wide (8 x 9 mm pitches). The removable comb busbar is already fitted — you can land feeders without extra bridging. Strip length 14 mm, torque to 3.5 N.m.","metaTitle":"Schneider Electric A9F68463 Acti9 iT60 MCB, 63 A, C Curve, 4","metaDescription":"Schneider A9F68463 Acti9 iT60 miniature circuit breaker, 63 A, C curve, 4 poles, 36 kA breaking capacity. Active production. Sourced to order. RFQ for current pricing.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Range":"Acti9","Width":"72 mm","Colour":"White","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"C","9 Mm Pitches":"8","Control type":"Toggle","Network type":"AC/DC","Product name":"Acti9 iT60","Mounting mode":"Removable comb busbar installed","Tropicalisation":"2 conforming to EN/IEC 60068-2-78","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iT60N","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"95 %","Tightening torque":"3.5 N.m top or bottom","Device application":"Distribution","Operating altitude":"0...2000 m","[In] rated current":"63 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Single terminal (top or bottom) 1...35 mm² rigid Single terminal (top or bottom) 1...25 mm² flexible","IP degree of protection":"IP20 B conforming to IEC 60529","Magnetic tripping limit":"8 x In +/- 20 %","Earth-leakage protection":"Without","Number of protected poles":"4","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 250 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/be/en/product/A9F68463/miniature-circuit-breaker-mcb-acti9-it60n-4p-63a-c-curve-6000a-iec-en-608981-10ka-iec-en-609472/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F68463/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of A9F68463 at 400 V?","answer":"At 380–415 V AC the Icu is 10 kA per IEC 60947-2, and the Icn per IEC 60898-1 is 10 kA at 400 V AC."},{"question":"Where can I buy the A9F68463 and get current pricing?","answer":"The A9F68463 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer."},{"question":"What compliance standards does the A9F68463 meet?","answer":"It is certified to EN/IEC 60898-1 and EN/IEC 60947-2, with suitability for isolation per both standards. Pollution degree 3 per IEC 60947-2 and tropicalisation class 2 per IEC 60068-2-78."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F68463","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F68463 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}