{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F75313","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F75313","canonicalUrl":"https://aoctrl.com/schneider/A9F75313","factsUrl":"https://aoctrl.com/api/mcp/products/A9F75313","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60N, miniature circuit breaker, 3P, 13 A, D curve, 36 kA Icu at 12-133 V AC, DIN rail mount, thermal-magnetic trip.","salesMarkdown":"The A9F75313 is a Schneider Acti9 iC60N miniature circuit breaker — 3-pole, 13 A rated current, D trip curve. The 36 kA Icu at 12-133 V AC (EN/IEC 60947-2) is the maximum fault current it can safely interrupt at that voltage range; at 220-240 V that drops to 20 kA, and at 380-415 V to 10 kA — still enough for most distribution panels behind a transformer. Dual-rated to both EN/IEC 60898-1 (the MCB standard) and EN/IEC 60947-2 (the industrial breaker standard), so it qualifies for either residential or industrial duty. Thermal-magnetic trip means the thermal bimetal handles overloads (slow, inverse-time), and the solenoid handles short circuits (instantaneous). IP20 finger-safe terminals, so it's fine inside an enclosure but not for wet locations. Dual-certified to EN/IEC 60898-1 (the household/ similar installation MCB standard) and EN/IEC 60947-2 (the low-voltage switchgear and controlgear standard for industrial applications). This dual rating is the key differentiator from a purely domestic MCB — it means the breaker is tested and marked for both duty classes, so it can be specified into an industrial panel without a separate industrial-grade breaker. Suitability for isolation is confirmed under both standards — you can safely use it as a disconnecting means.","metaTitle":"Schneider A9F75313 Acti9 iC60N MCB, D Curve 13A 3P 36kA","metaDescription":"Schneider A9F75313 Acti9 iC60N miniature circuit breaker, 13A D curve 3-pole, 36kA breaking capacity. Dual-rated EN/IEC 60947-2 & 60898-1. Available to order, RFQ for current prici","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"54 mm","Colour":"White","Height":"85 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"D","9 Mm Pitches":"6","Control type":"Toggle","Network type":"AC DC","Product name":"Acti9 iC60","Mounting mode":"Fixed","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"IC60N","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","Operating altitude":"0...2000 m","[In] rated current":"13 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Single terminal (top or bottom) 1...25 mm² rigid Single terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"12 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 180 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2","Comb busbar and distribution block compatibility":"Top or bottom: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/49d9ec2d1cab6f17f85013acde9ffc01.pdf","sourceUrl":"https://www.se.com/hk/en/product/A9F75313/miniature-circuit-breaker-mcb-acti9-ic60n-3p-13a-d-curve-6000a-iec-en-608981-10ka-iec-en-609472/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F75313/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for A9F75313?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution channels. Submit an RFQ for current pricing and confirmed availability at the time of your order — no online stock figure can reflect real-time allocation."},{"question":"What is A9F75313's listed depth?","answer":"The A9F75313 has a depth of 78.5 mm (mounting depth on the DIN rail). Overall height is 85 mm, width is 54 mm (6 x 9 mm pitches)."},{"question":"What compliance documentation does this brand provide for A9F75313?","answer":"Schneider provides the standard compliance package for the Acti9 iC60N series: the breaker is certified to EN/IEC 60898-1 and EN/IEC 60947-2, carries IP20 protection (IEC 60529), and is tropicalised per IEC 60068-1 class 2. RoHS and REACH declarations are available from Schneider's documentation portal for the Acti9 range."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F75313","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F75313 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}