{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F76106","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F76106","canonicalUrl":"https://aoctrl.com/schneider/A9F76106","factsUrl":"https://aoctrl.com/api/mcp/products/A9F76106","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Acti9 iC60 A9F76106 miniature circuit breaker, 1-pole, B-curve, 6 A switching current, 36 kA breaking capacity (Icu) per IEC 60947-2, thermal-magnetic trip unit, 60 V AC/DC, clip-on mounting, IP20.","salesMarkdown":"## Overview The A9F76106 is a Schneider Acti9 iC60 miniature circuit breaker with one pole, a B-curve trip characteristic, and a 6 A switching current rating. Its breaking capacity reaches 36 kA (Icu) per EN/IEC 60947-2, making it suitable for distribution panels where moderate fault levels are expected. The thermal-magnetic trip unit handles both overload and short-circuit protection on AC or DC networks up to 60 V.","metaTitle":"Schneider A9F76106 Acti9 iC60 MCB, 1-pole B-curve 6 A 36 kA","metaDescription":"Schneider Acti9 iC60 A9F76106 miniature circuit breaker, 1-pole, B-curve, 6 A, 36 kA breaking capacity per IEC 60947-2. Active part, RFQ for lead time.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"85 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"B","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC DC","Product name":"Acti9 iC60","Mounting mode":"Clip-on Removable comb busbar installed","Product weight":"0.215 kg","Quality labels":"NF","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Connection pitch":"18 mm between devices","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"35 mm DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"36 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2 10 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"IC60N","Network frequency":"50/60 Hz","Poles description":"1P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","Operating altitude":"0...2000 m","[In] rated current":"6 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Single terminal (top or bottom) , for 1 cable(s) , 1...25 mm², rigid, copper Single terminal (top or bottom) , for 1 cable(s) , 1...16 mm², flexible, copper Single terminal (top or bottom) , for 1 cable(s) , 1...16 mm², flexible with ferrule, copper Single terminal (top or bottom) , for 1.0 cable(s) , flexible, copper or aluminium, with ring terminal and accessory","IP degree of protection":"IP20 conforming to IEC 60529 IP40 in modular enclosure (Insulation class II) conforming to IEC 60529","Magnetic tripping limit":"4 x In +/- 20 %","Earth-leakage protection":"Without","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","[Ue] rated operational voltage":"12...60 V AC 50/60 Hz 100...133 V AC 50/60 Hz 220...240 V AC 50/60 Hz 12...60 V DC 60...72 V DC","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"27 kA 75 % x Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA 75 % x Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 7.5 kA 75 % x Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA 100 % x Icu at 12...60 V DC conforming to EN/IEC 60947-2 10 kA 100 % x Icu at 60...72 V DC conforming to EN/IEC 60947-2","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2","Comb busbar and distribution block compatibility":"Top or bottom: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$21.97","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1f58fd0030fa1053337a5b168cee5e6d.pdf","sourceUrl":"https://www.se.com/eg/en/product/A9F76106/miniature-circuit-breaker-mcb-acti9-ic60n-1p-6a-b-curve-6000a-iec-en-608981-10ka-iec-en-609472/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F76106/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F76106","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F76106 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}