{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F92404","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F92404","canonicalUrl":"https://aoctrl.com/schneider/A9F92404","factsUrl":"https://aoctrl.com/api/mcp/products/A9F92404","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Acti9 iC60 A9F92404 miniature circuit breaker, 4-pole, 4 A, Z-curve, 100 kA ICU, AC/DC, 133 V, thermal-magnetic trip, IP20, clip-on mounting.","salesMarkdown":"## Overview The A9F92404 is a Schneider Acti9 iC60 miniature circuit breaker with 4 poles, rated 4 A on a Z-curve, and an ultimate breaking capacity (Icu) of 100 kA. It operates on both AC and DC networks at 133 V supply voltage, using a thermal-magnetic trip unit. The Z-curve provides magnetic tripping at 3 x In +/- 20 %, suited for protecting sensitive electronic loads where low inrush tolerance is required. The A9F92404 is an active, in-production part within Schneider's Acti9 iC60 range. For a firm lead time and quantity, submit an RFQ — the part is widely available through distribution channels.","metaTitle":"Schneider A9F92404 iC60 MCB, 4-pole, 4 A, Z-curve, 100 kA","metaDescription":"Schneider Acti9 iC60 A9F92404 miniature circuit breaker, 4-pole, 4 A, Z-curve, 100 kA ICU, AC/DC, 133 V, EN/IEC 60947-2 & 60898-1.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"72 mm","Colour":"White","Height":"85 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"Z","9 Mm Pitches":"8","Control type":"Toggle","Network type":"AC DC","Product name":"Acti9 iC60","Mounting mode":"Clip-on Removable comb busbar installed","Product weight":"0.5 kg","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Connection pitch":"18 mm between phases","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"35 mm DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"100 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 100 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 100 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 15000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iC60L","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","Operating altitude":"0...2000 m","[In] rated current":"4 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Single terminal (top or bottom) , for 1 cable(s) , 1...25 mm², rigid, copper Single terminal (top or bottom) , for 1 cable(s) , 1...16 mm², flexible, copper Single terminal (top or bottom) , for 1 cable(s) , 1...16 mm², flexible with ferrule, copper Single terminal (top or bottom) , for 1.0 cable(s) , flexible, copper or aluminium, with ring terminal and accessory","IP degree of protection":"IP20 conforming to IEC 60529 IP40 in modular enclosure (Insulation class II) conforming to IEC 60529","Magnetic tripping limit":"3 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"4","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2 Yes conforming to EN/IEC 60898-1","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","[Ue] rated operational voltage":"12...133 V AC 50/60 Hz 220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz 440 V AC 50/60 Hz <= 250 V DC","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"100 kA 100 % x Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 100 kA 100 % x Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 100 kA 100 % x Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA 100 % x Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA 100 % x Icu at <= 250 V DC conforming to EN/IEC 60947-2","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2","Comb busbar and distribution block compatibility":"Top or bottom: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$548.23","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c40d85c8dac1d9701cce0e33a53b5a9e.pdf","sourceUrl":"https://www.se.com/vn/en/product/A9F92404/ic60l-miniature-circuit-breaker-4p-4a-z-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F92404/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F92404","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F92404 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}