{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F95320","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F95320","canonicalUrl":"https://aoctrl.com/schneider/A9F95320","factsUrl":"https://aoctrl.com/api/mcp/products/A9F95320","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Acti9 iC60L A9F95320 miniature circuit breaker, 3-pole, 20 A, K-curve, 70 kA ICu, 133 V AC/DC, thermal-magnetic trip unit, clip-on mounting, IP20.","salesMarkdown":"## Overview The A9F95320 is a Schneider Acti9 iC60L miniature circuit breaker with 3 poles, rated 20 A on a K-curve, and a breaking capacity of 70 kA ICu. It operates on 133 V AC/DC networks and uses a thermal-magnetic trip unit. The part is in active production and widely available through distribution. ## Compliance & standards Utilization category A per EN/IEC 60947-2 applies. Clip-on mounting with removable comb busbar. Terminal pitch is 18 mm between phases. Single terminal top or bottom accepts 1…25 mm² rigid copper or 1…16 mm² flexible copper, with or without ferrule. Torque setting 2 N.m top or bottom.","metaTitle":"Schneider A9F95320 iC60L MCB, 3-pole, 20 A, K-curve, 70 kA","metaDescription":"Schneider Acti9 iC60L A9F95320 miniature circuit breaker, 3-pole, 20 A, K-curve, 70 kA ICu, 133 V AC/DC, thermal-magnetic trip, EN/IEC 60947-2 and 60898-1.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"54 mm","Colour":"White","Height":"85 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"K","9 Mm Pitches":"6","Control type":"Toggle","Network type":"AC DC","Product name":"Acti9 iC60","Mounting mode":"Clip-on Removable comb busbar installed","Product weight":"0.375 kg","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Connection pitch":"18 mm between phases","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"35 mm DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"70 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 15000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iC60L","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","Operating altitude":"0...2000 m","[In] rated current":"20 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Single terminal (top or bottom) , for 1 cable(s) , 1...25 mm², rigid, copper Single terminal (top or bottom) , for 1 cable(s) , 1...16 mm², flexible, copper Single terminal (top or bottom) , for 1 cable(s) , 1...16 mm², flexible with ferrule, copper Single terminal (top or bottom) , for 1.0 cable(s) , flexible, copper or aluminium, with ring terminal and accessory","IP degree of protection":"IP20 conforming to IEC 60529 IP40 in modular enclosure (Insulation class II) conforming to IEC 60529","Magnetic tripping limit":"12 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2 Yes conforming to EN/IEC 60898-1","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","[Ue] rated operational voltage":"12...133 V AC 50/60 Hz 220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz 440 V AC 50/60 Hz <= 180 V DC","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"35 kA 50 % x Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA 50 % x Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 12.5 kA 50 % x Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA 50 % x Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA 100 % x Icu at <= 180 V DC conforming to EN/IEC 60947-2","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2","Comb busbar and distribution block compatibility":"Top or bottom: YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$403.30","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9e7e975c7e870dee5c1975d3bdba2b41.pdf","sourceUrl":"https://www.se.com/nz/en/product/A9F95320/miniature-circuit-breaker-mcb-acti9-ic60l-3p-20a-k-curve-15000a-iec-en-608981-25ka-iec-en-609472/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F95320/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F95320","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F95320 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}