{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9FDB606","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9FDB606","canonicalUrl":"https://aoctrl.com/schneider/A9FDB606","factsUrl":"https://aoctrl.com/api/mcp/products/A9FDB606","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iDPN N Arc, arc fault detection circuit breaker (AFDD), 1P+N, 6 A rated current, C-curve, 6 kA breaking capacity, DIN rail mount.","salesMarkdown":"## Arc fault detection circuit breaker, 6 A C-curve, 1P+N The Schneider Electric A9FDB606 is an Acti9 iDPN N Arc arc fault detection circuit breaker (AFDD) combining overcurrent protection with series arc-fault detection in a single 1P+N module. Rated 6 A at 30 °C with a C-curve magnetic trip (5...10 x In), it breaks 6000 A Icn at 230 V AC 50 Hz per EN/IEC 60898-1. The thermal-magnetic trip unit covers overload and short-circuit; the arc-fault electronics detect hazardous series arcing downstream and trip the circuit independently of the overcurrent mechanism. The 6 kA breaking capacity at 230 V AC is the maximum fault current it can safely interrupt; this matches typical domestic and light commercial panel fault levels (IEC 60898-1). Limitation class 3 means it restricts let-through energy under short-circuit, reducing stress on downstream wiring and devices. Clip-on mounting to DIN rail, 36 mm wide (2 modular spaces), 81 mm tall, 72 mm deep. Neutral on the left, phase on the right — tunnel terminals accept up to 16 mm² rigid or 10 mm² flexible (single cable), or 2.5 mm² for two cables. Tightening torque 2 N·m, strip length 14 mm. The 9 mm pitch between phase and neutral terminals matches standard Acti9 busbar spacing.","metaTitle":"Schneider Electric A9FDB606 Acti9 iDPN N Arc, 6A C-curve AFD","metaDescription":"Schneider Electric A9FDB606 Acti9 iDPN N Arc arc fault detection circuit breaker, 6A C-curve, 6kA breaking capacity, 1P+N, DIN rail mount. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"72 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"81 mm","Standards":"EN/IEC 62606 IEC 60898-1","Curve code":"C","Cable Entry":"Top","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iDPN N Arc","Mounting mode":"Clip-on","Tropicalisation":"Severity B conforming to IEC 60068-2-30 for 28 d","lifecycle_stage":"current","Connection pitch":"9 mm between phase and neutral","Limitation class":"3 conforming to IEC 60898-1","Local signalling":"ON, OFF, fault trip","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"2","Breaking capacity":"6000 A Icn at 230 V AC 50 Hz conforming to EN/IEC 60898-1","Device short name":"iDPN N Arc","Network frequency":"50 Hz","Poles description":"1P + N","Tightening torque":"2 N.m","Operating altitude":"2000 m","[In] rated current":"6 A at 30 °C","Overvoltage category":"III","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles 230 V AC 50 Hz","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm","Connections - terminals":"Tunnel type terminal for 1 cable(s) 10 mm² flexible Tunnel type terminal for 2 cable(s) 2.5 mm² flexible Tunnel type terminal for 1 cable(s) 16 mm² rigid Tunnel type terminal for 2 cable(s) 2.5 mm² rigid","IP degree of protection":"IP20","Magnetic tripping limit":"5...10 x In","Device location in system":"Outgoer","Number of protected poles":"1","Product or component type":"Arc fault detection circuit breaker","Contact position indicator":"Yes","Threshold tripping voltage":"400 V 200 ms","Product specific application":"Fire prevention by arc detection","[Ui] rated insulation voltage":"400 V AC","[Ue] rated operational voltage":"230 V AC 50 Hz conforming to IEC 62606 230 V AC 50 Hz conforming to EN/IEC 60898-1","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...60 °C","[Uimp] rated impulse withstand voltage":"4 kV conforming to IEC 60898-1","Comb busbar and distribution block compatibility":"ProDis Librio"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1d3427f3bfb6ad4844a00420d5ba29c3.pdf","sourceUrl":"https://www.se.com/nl/en/product/A9FDB606/acti9-idpn-n-arc-1p+n-6a-c-6000a-arc-fault-detection-circuit-breaker/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9FDB606/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of A9FDB606?","answer":"The A9FDB606 has a breaking capacity of 6000 A Icn at 230 V AC 50 Hz, conforming to EN/IEC 60898-1."},{"question":"Where can I buy A9FDB606 and how is it quoted?","answer":"The A9FDB606 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What standards does A9FDB606 comply with?","answer":"The A9FDB606 complies with EN/IEC 62606 (arc fault detection devices) and IEC 60898-1 (circuit-breakers for overcurrent protection)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9FDB606","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9FDB606 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}