{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9HC54S160","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9HC54S160","canonicalUrl":"https://aoctrl.com/schneider/A9HC54S160","factsUrl":"https://aoctrl.com/api/mcp/products/A9HC54S160","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 distribution board, A9HC54S160, 54-way, 160 A rated operational current at 240/415 V AC, IP40, surface-mount single-door enclosure, white (RAL 9003).","salesMarkdown":"The Schneider Electric A9HC54S160 is a 54-way distribution board from the Acti9 range, fitted with a 160 A main incomer isolator and pre-populated outgoers: a 63 A MCB and a 63 A RCBO. Rated operational current is 160 A at 240/415 V AC, with a rated insulation voltage of 500 V and impulse withstand of 6 kV — sized for a standard commercial or light industrial sub-main. The enclosure is powder-coated sheet steel, surface-mount, with a plain door, IP40 protection (tools and small wires kept out, but not sealed against water — keep it indoors). This part is marked obsolete by the manufacturer. No official successor order code is listed in the record. ## What's in the box Supplied with the enclosure, earthing bar, pan assembly, removable gland plates at top and bottom, isolator, and neutral bar — ready for panel wiring.","metaTitle":"Schneider Electric A9HC54S160 Acti9 Distribution Board, 54 W","metaDescription":"Schneider Electric A9HC54S160 Acti9 distribution board, 54 ways, 160 A rated operational current, IP40, surface mount. Obsolete — sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"External : 140 mm","Range":"Acti9","Width":"External: 470 mm","Colour":"White (RAL 9003)","Height":"External: 1078 mm","Door type":"Plain","Standards":"AS/NZS 61439-3","Number of ways":"54 ways","lifecycle_stage":"current","Device application":"Distribution","Enclosure material":"Powder coated sheet steel","Enclosure mounting":"Surface","Provided equipment":"Enclosure Earthing bar Pan assembly Removable gland plates at top and bottom of the enclosure Isolator Neutral bar","Protection device type":"Main incomer: isolator - 160 A Outgoer: miniature circuit breaker (MCB) - 63 A Outgoer: residual current circuit breaker with overcurrent protection (RCBO) - 63 A","IP degree of protection":"IP40","Product or component type":"Distribution board","Enclosure/cubicle description":"Single door enclosure","[Ui] rated insulation voltage":"500 V","[Ie] rated operational current":"160 A at 240/415 V AC","Ambient air temperature for operation":"-15...50 °C","[Uimp] rated impulse withstand voltage":"6 kV","[Icw] rated short-time withstand current":"25 kA for 100 ms"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/au/en/product/A9HC54S160/distribution-board-acti9-ip40-54-way-fitted-with-160a-incomer/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9HC54S160/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9HC54S160 and how do I get a price?","answer":"The A9HC54S160 is sourced to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."},{"question":"What is A9HC54S160's listed depth?","answer":"The external depth is 140 mm."},{"question":"What is A9HC54S160's listed range?","answer":"It belongs to the Schneider Electric Acti9 range."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9HC54S160","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9HC54S160 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}