{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9K14306","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9K14306","canonicalUrl":"https://aoctrl.com/schneider/A9K14306","factsUrl":"https://aoctrl.com/api/mcp/products/A9K14306","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iK60N, miniature circuit-breaker, 3P, C-curve, 6 A, 4500 A Icn at 400 V AC, thermal-magnetic, clip-on DIN rail.","salesMarkdown":"The Schneider Electric A9K14306 is an Acti9 iK60N miniature circuit breaker — 3 poles, C-curve, rated 6 A at 30 °C. It breaks 4500 A at 400 V AC (EN/IEC 60898-1), which is the standard fault level for residential and light-commercial distribution boards in most of Europe and Asia. Thermal-magnetic trip with a magnetic threshold of 5 to 10 times In means it holds motor inrush and transformer magnetising current without nuisance tripping, yet still clears a hard short fast. The C-curve is the default for general-purpose distribution — lighting, small motor loads, socket circuits — where you need a bit of headroom above the B-curve. IP20 finger-safe, rated for isolation, and carries a padlocking option. Accepts 1 to 25 mm² rigid copper — plenty for the 6 A load circuit. The ON/OFF toggle gives a visible isolation point; the padlock hasp accepts a standard 4 mm shackle for LOTO procedures.","metaTitle":"Schneider Electric A9K14306 Acti9 iK60 MCB, 3P C-Curve 6 A,","metaDescription":"Schneider A9K14306 Acti9 iK60N miniature circuit breaker, 3-pole, C-curve, 6 A rated, 4500 A breaking capacity at 400 V AC. EN/IEC 60898-1. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Circuit Breaker Accessories"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"54 mm","Colour":"White","Height":"85 mm","Standards":"EN/IEC 60898-1","Curve code":"C","9 Mm Pitches":"6","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iK60","Mounting mode":"Clip-on","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"ON/OFF indication","Mounting support":"DIN rail","Pollution degree":"2 conforming to EN/IEC 60898-1","Breaking capacity":"4500 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iK60N","Network frequency":"50/60 Hz","Poles description":"3P","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"6 A at 30 °C","Overvoltage category":"III","Trip unit technology":"Thermal-magnetic","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Tunnel type terminal (top or bottom) 1...25 mm² rigid","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Without","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1","Locking options description":"Padlocking device","[Ui] rated insulation voltage":"440 V AC 50/60 Hz conforming to EN/IEC 60898-1","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"4500 A 100 % conforming to EN/IEC 60898-1 - 400 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"4 kV conforming to EN/IEC 60898-1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d16af9bab52584eb9f62c306533245a8.pdf","sourceUrl":"https://www.se.com/id/en/product/A9K14306/ik60a-miniature-circuit-breaker-3p-6-a-c-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9K14306/alternatives.json"},"ai":{"faq":[{"question":"What is A9K14306's breaking capacity?","answer":"4500 A Icn at 400 V AC 50/60 Hz, conforming to EN/IEC 60898-1. That is the standard short-circuit rating for residential and light-commercial distribution boards."},{"question":"What does the C-curve mean on this breaker?","answer":"The C-curve means the magnetic trip threshold is 5 to 10 times the rated current (In). It holds moderate inrush from small motors and transformers without nuisance tripping, while still clearing hard shorts quickly. It is the standard choice for general-purpose distribution circuits."},{"question":"What compliance documentation does Schneider provide for A9K14306?","answer":"The breaker is certified to EN/IEC 60898-1, with pollution degree 2 and overvoltage category III. It carries an IP20 finger-safe rating. Standard Schneider documentation includes the declaration of conformity for CE marking."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9K14306","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9K14306 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}