{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9K23106","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9K23106","canonicalUrl":"https://aoctrl.com/schneider/A9K23106","factsUrl":"https://aoctrl.com/api/mcp/products/A9K23106","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iK60N, A9K23106, miniature circuit breaker, 1P, 6 A, B curve, 6 kA Icn at 230 V AC, clip-on DIN rail mount.","salesMarkdown":"The Schneider Electric A9K23106 is an Acti9 iK60N miniature circuit breaker (MCB) rated 6 A at 30 °C, single pole, B-curve trip characteristic, with a 6 kA breaking capacity (Icn) at 230 V AC per EN/IEC 60898-1. At 18 mm wide (2 x 9 mm pitches), this MCB occupies a single module on the DIN rail. Depth is 78.5 mm, height 85 mm — standard for the Acti9 family, so it aligns with adjacent breakers and accessories in the same enclosure. Limitation class 3. Thermal-magnetic trip unit, no earth-leakage protection integrated. Rated insulation voltage 440 V AC. Electrical durability 10,000 cycles, mechanical 20,000 cycles. Storage temperature range -40 to 85 °C.","metaTitle":"Schneider Electric A9K23106 Acti9 iK60N MCB, 6 A, 1P, B Curv","metaDescription":"Schneider Electric A9K23106 Acti9 iK60N miniature circuit breaker, 6 A rated, 1 pole, B curve, 6 kA breaking capacity per EN/IEC 60898-1. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"85 mm","Standards":"EN/IEC 60898-1","Curve code":"B","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iK60","Mounting mode":"Clip-on","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"ON/OFF indication","Mounting support":"DIN rail","Pollution degree":"2 conforming to EN/IEC 60898-1","Breaking capacity":"6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iK60N","Network frequency":"50/60 Hz","Poles description":"1P","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"6 A at 30 °C","Overvoltage category":"III","Trip unit technology":"Thermal-magnetic","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Tunnel type terminal (top or bottom) 1...25 mm² rigid Tunnel type terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"3...5 x In","Earth-leakage protection":"Without","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1","Contact position indicator":"No","Locking options description":"Padlocking device","[Ui] rated insulation voltage":"440 V AC 50/60 Hz conforming to EN/IEC 60898-1","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"6000 A 100 % conforming to EN/IEC 60898-1 - 230 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"4 kV conforming to EN/IEC 60898-1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9K23106/miniature-circuit-breaker-mcb-acti9-ik60n-1p-6a-b-curve-6000a-iec-en-608981/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9K23106/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of the A9K23106?","answer":"6,000 A Icn at 230 V AC, 50/60 Hz, conforming to EN/IEC 60898-1."},{"question":"What is the A9K23106 used for?","answer":"It is a 6 A single-pole B-curve MCB for AC distribution circuits — typically lighting, small transformers, or resistive loads in residential or commercial panels."},{"question":"What compliance documentation is available for the A9K23106?","answer":"The MCB is certified to EN/IEC 60898-1, with pollution degree 2 and overvoltage category III. The manufacturer provides standard declarations of conformity; specific RoHS/REACH/UL documentation should be requested at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9K23106","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9K23106 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}