{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9K23232","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9K23232","canonicalUrl":"https://aoctrl.com/schneider/A9K23232","factsUrl":"https://aoctrl.com/api/mcp/products/A9K23232","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iK60N, A9K23232, miniature circuit breaker, 32 A, B-curve, 2P, 6000 A Icn at 400 V AC, thermal-magnetic, clip-on DIN rail.","salesMarkdown":"The Schneider Electric A9K23232 is an Acti9 iK60N miniature circuit breaker rated 32 A at 30 °C, B-curve, 2-pole, with a 6000 A Icn breaking capacity at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1. Clip-on mounting on a 36 mm wide DIN rail, occupying 4 x 9 mm pitches. The 2-pole body is 36 mm wide, 85 mm tall, 78.5 mm deep — fits standard distribution boards and sub-panels. Tunnel terminals accept 1 to 25 mm² rigid or 1 to 16 mm² flexible cable; tighten to 3.5 N.m. Strip 14 mm of insulation. Padlocking provision for lockout/tagout.","metaTitle":"Schneider Electric A9K23232 Acti9 iK60N MCB, 32 A B-Curve 2P","metaDescription":"Schneider Electric A9K23232 Acti9 iK60N miniature circuit breaker, 32 A rated current, B-curve, 2-pole, 6 kA breaking capacity at 400 V AC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"85 mm","Standards":"EN/IEC 60898-1","Curve code":"B","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iK60","Mounting mode":"Clip-on","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"ON/OFF indication","Mounting support":"DIN rail","Pollution degree":"2 conforming to EN/IEC 60898-1","Breaking capacity":"6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iK60N","Network frequency":"50/60 Hz","Poles description":"2P","Tightening torque":"3.5 N.m top or bottom","Device application":"Distribution","[In] rated current":"32 A at 30 °C","Overvoltage category":"III","Trip unit technology":"Thermal-magnetic","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Tunnel type terminal (top or bottom) 1...25 mm² rigid Tunnel type terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"3...5 x In","Earth-leakage protection":"Without","Number of protected poles":"2","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1","Contact position indicator":"No","Locking options description":"Padlocking device","[Ui] rated insulation voltage":"440 V AC 50/60 Hz conforming to EN/IEC 60898-1","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"6000 A 100 % conforming to EN/IEC 60898-1 - 400 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"4 kV conforming to EN/IEC 60898-1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9K23232/miniature-circuit-breaker-mcb-acti9-ik60n-2p-32a-b-curve-6000a-iec-en-608981/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9K23232/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9K23232?","answer":"The A9K23232 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is A9K23232's breaking capacity?","answer":"The A9K23232 has a 6000 A Icn breaking capacity at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1. This means it safely interrupts fault currents up to 6 kA in a 400 V distribution circuit."},{"question":"What is the B-curve on this MCB?","answer":"The B-curve means the magnetic trip operates at 3 to 5 times the rated current (In). For the 32 A A9K23232, that's 96 to 160 A instantaneous trip — suited for resistive loads and general-purpose circuits with low inrush."},{"question":"What compliance documentation does Schneider provide for A9K23232?","answer":"The A9K23232 is designed and tested to EN/IEC 60898-1. It carries CE marking for the European market. For specific RoHS, REACH, or UL documentation, request the compliance declaration at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9K23232","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9K23232 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}