{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9K23325","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9K23325","canonicalUrl":"https://aoctrl.com/schneider/A9K23325","factsUrl":"https://aoctrl.com/api/mcp/products/A9K23325","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iK60, miniature circuit breaker, A9K23325, 3P, 25 A, B curve, 6 kA Icn at 400 V AC, thermal-magnetic trip, DIN rail mount.","salesMarkdown":"The Schneider Electric A9K23325 is a 3-pole miniature circuit breaker from the Acti9 iK60 series, rated 25 A at 30 °C with a B tripping curve (magnetic trip between 3 and 5 times In). The B curve means it's sized for resistive and general-purpose loads — lighting, small transformers, control circuits — where inrush is modest and you want fast clearing on short circuits. The 6 kA breaking capacity at 400 V AC (Icn per EN/IEC 60898-1) tells you it can safely interrupt a fault up to that level on a 400 V three-phase network; for most domestic and light commercial distribution boards that's adequate, but if your prospective short-circuit current exceeds 6 kA you step up to an iC60 or a higher-rated series. The thermal-magnetic trip unit combines a bimetal strip for overload protection and a solenoid for short-circuit protection. The 3-pole body takes 6 module pitches (9 mm each, so 54 mm total width). Depth is 78.5 mm, height 85 mm. IP20 front face — fine for enclosed panels, not for washdown environments. ## What compliance documentation is available The manufacturer provides a Declaration of Conformity covering the applicable directives; RoHS and REACH compliance data is published in the product environmental profile. No UL or CSA listing is cited on this variant — it's designed for IEC-market panels.","metaTitle":"Schneider Electric A9K23325 Acti9 iK60 MCB, 25 A, 3P, B Curv","metaDescription":"Schneider Electric A9K23325 Acti9 iK60N miniature circuit breaker, 25 A rated current, 3 poles, B curve, 6 kA breaking capacity at 400 V AC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Circuit Breaker Accessories"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"54 mm","Colour":"White","Height":"85 mm","Standards":"EN/IEC 60898-1","Curve code":"B","9 Mm Pitches":"6","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iK60","Mounting mode":"Clip-on","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"ON/OFF indication","Mounting support":"DIN rail","Pollution degree":"2 conforming to EN/IEC 60898-1","Breaking capacity":"6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iK60N","Network frequency":"50/60 Hz","Poles description":"3P","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"25 A at 30 °C","Overvoltage category":"III","Trip unit technology":"Thermal-magnetic","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Tunnel type terminal (top or bottom) 1...25 mm² rigid Tunnel type terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"3...5 x In","Earth-leakage protection":"Without","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1","Contact position indicator":"No","Locking options description":"Padlocking device","[Ui] rated insulation voltage":"440 V AC 50/60 Hz conforming to EN/IEC 60898-1","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"6000 A 100 % conforming to EN/IEC 60898-1 - 400 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"4 kV conforming to EN/IEC 60898-1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9K23325/miniature-circuit-breaker-mcb-acti9-ik60n-3p-25a-b-curve-6000a-iec-en-608981/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9K23325/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy the A9K23325 and get a price?","answer":"We source the A9K23325 to order against an RFQ. Submit a request and we'll confirm availability and current pricing at quote time through our supply channels."},{"question":"What is the A9K23325's breaking capacity?","answer":"It is rated 6000 A Icn at 400 V AC, 50/60 Hz, conforming to EN/IEC 60898-1. That's the maximum fault current it can safely interrupt at rated voltage."},{"question":"What is the closest alternative to the A9K23325 in the Acti9 family?","answer":"Within the same iK60N series, the closest sibling would be a 3-pole unit with a different current rating or curve — same footprint, same breaking capacity. If you need higher interrupting capacity (10 kA or more), the Acti9 iC60 series is the next step up, but it's a different mechanical platform."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9K23325","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9K23325 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}