{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9K23410","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9K23410","canonicalUrl":"https://aoctrl.com/schneider/A9K23410","factsUrl":"https://aoctrl.com/api/mcp/products/A9K23410","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iK60N, A9K23410, miniature circuit-breaker, 4P, 10 A, curve B, 6000 A Icn at 400 V AC, thermal-magnetic, DIN rail clip-on.","salesMarkdown":"The A9K23410 is a 4-pole miniature circuit-breaker from the Acti9 iK60N series, rated 10 A at 30 °C with a B-curve magnetic trip threshold of 3 to 5 times In. The thermal-magnetic trip unit combines a bimetal element for overload protection (time-delayed, inverse-time curve) with a solenoid for instantaneous short-circuit protection. Clip-on mounting to a 35 mm DIN rail (EN 60715) is standard; the 4-pole body occupies 8 modules of 9 mm pitch, for a total width of 72 mm. Depth is 78.5 mm, height 85 mm — fits standard distribution boards and enclosure cut-outs. Tunnel-type terminals accept 1 to 25 mm² rigid or 1 to 16 mm² flexible cable; tightening torque is 2 N.m. IP20 finger-safe terminals suit installation in enclosed panels; no additional touch-protection shrouds are required for the front face.","metaTitle":"Schneider Electric A9K23410 Acti9 iK60N MCB, 4P, 10 A, Curve","metaDescription":"Schneider Electric A9K23410 Acti9 iK60N miniature circuit-breaker, 4P, 10 A, curve B, 6 kA breaking capacity at 400 V AC, EN/IEC 60898-1. Sourced to order against an RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Circuit Breaker Accessories"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"72 mm","Colour":"White","Height":"85 mm","Standards":"EN/IEC 60898-1","Curve code":"B","9 Mm Pitches":"8","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iK60","Mounting mode":"Clip-on","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"ON/OFF indication","Mounting support":"DIN rail","Pollution degree":"2 conforming to EN/IEC 60898-1","Breaking capacity":"6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iK60N","Network frequency":"50/60 Hz","Poles description":"4P","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"10 A at 30 °C","Overvoltage category":"III","Trip unit technology":"Thermal-magnetic","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Tunnel type terminal (top or bottom) 1...25 mm² rigid Tunnel type terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"3...5 x In","Earth-leakage protection":"Without","Number of protected poles":"4","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1","Contact position indicator":"No","Locking options description":"Padlocking device","[Ui] rated insulation voltage":"440 V AC 50/60 Hz conforming to EN/IEC 60898-1","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"6000 A 100 % conforming to EN/IEC 60898-1 - 400 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"4 kV conforming to EN/IEC 60898-1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9K23410/miniature-circuit-breaker-ik60n-4p-10-a-b-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9K23410/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for A9K23410?","answer":"The A9K23410 is sourced and quoted to order against an RFQ; availability and current pricing are confirmed at quote time through independent distribution channels."},{"question":"What is A9K23410's listed depth?","answer":"The A9K23410 has a depth of 78.5 mm."},{"question":"What compliance documentation does this brand provide for A9K23410?","answer":"The A9K23410 is certified to EN/IEC 60898-1, with pollution degree 2 and overvoltage category III. It carries the CE mark as part of the Schneider Acti9 range; RoHS and REACH declarations are standard from the manufacturer."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9K23410","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9K23410 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}