{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9K23604","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9K23604","canonicalUrl":"https://aoctrl.com/schneider/A9K23604","factsUrl":"https://aoctrl.com/api/mcp/products/A9K23604","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iK60N, miniature circuit breaker, 1P+N, 4 A, B curve, 6 kA Icn at 230 V AC, EN/IEC 60898-1, thermal-magnetic, DIN rail clip-on.","salesMarkdown":"The Schneider Electric A9K23604 is an Acti9 iK60N miniature circuit breaker (MCB) — a 1P+N unit rated 4 A at 30 °C with a B tripping curve and a 6 kA breaking capacity at 230 V AC, certified to EN/IEC 60898-1. It clips onto standard DIN rail (EN 60715) and takes up 4 module pitches at 9 mm each — 36 mm wide total. That's a standard 1P+N footprint for a single-module-width neutral on the left. The toggle handle gives local ON/OFF indication; no auxiliary contact position indicator on this variant. IP20 rated for the front face — fine inside a panel, not for wet environments.","metaTitle":"Schneider Electric A9K23604 Acti9 iK60N MCB, B Curve 4 A 1P+","metaDescription":"Schneider Electric A9K23604 Acti9 iK60N miniature circuit breaker, B curve 4 A, 1P+N, 6 kA breaking capacity per EN/IEC 60898-1. Current production. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"85 mm","Standards":"EN/IEC 60898-1","Curve code":"B","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iK60","Mounting mode":"Clip-on","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"ON/OFF indication","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"2 conforming to EN/IEC 60898-1","Breaking capacity":"6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iK60N","Network frequency":"50/60 Hz","Poles description":"1P + N","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"4 A at 30 °C","Overvoltage category":"III","Trip unit technology":"Thermal-magnetic","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Single terminal (top or bottom) 1...25 mm² rigid","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"3...5 x In","Earth-leakage protection":"Without","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1","Contact position indicator":"No","Locking options description":"Padlocking device","[Ui] rated insulation voltage":"440 V AC 50/60 Hz conforming to EN/IEC 60898-1","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"6000 A 100 % conforming to EN/IEC 60898-1 - 230 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"4 kV conforming to EN/IEC 60898-1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9ba04ec86e6212dd8a79029a8c88e502.pdf","sourceUrl":"https://www.se.com/in/en/product/A9K23604/miniature-circuit-breaker-ik60n-1p-+-n-4-a-b-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9K23604/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9K23604 and how do I get a price?","answer":"The A9K23604 is sourced and quoted to order against an RFQ through independent distribution. Submit a request for quote (RFQ) to confirm current availability and pricing at the time of your order."},{"question":"What is A9K23604's breaking capacity and what does it mean?","answer":"The A9K23604 has a 6000 A Icn breaking capacity at 230 V AC per EN/IEC 60898-1. That means it can safely interrupt a fault current up to 6000 A without failing — adequate for most final distribution circuits where the prospective short-circuit current is below that level."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9K23604","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9K23604 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}