{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9K23616","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9K23616","canonicalUrl":"https://aoctrl.com/schneider/A9K23616","factsUrl":"https://aoctrl.com/api/mcp/products/A9K23616","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iK60N, miniature circuit breaker, 16 A, curve B, 1P+N, 6 kA Icn at 230 V AC, EN/IEC 60898-1.","salesMarkdown":"The Schneider Electric A9K23616 is an Acti9 iK60N miniature circuit breaker rated 16 A at 30 °C, curve B, 1P+N configuration. The thermal-magnetic trip unit gives a magnetic threshold of 3 to 5 x In, so it clears short-circuit faults fast while tolerating inrush from resistive loads like heaters or lighting banks. Depth is 78.5 mm, height 85 mm — the 78.5 mm depth matters when the gland plate or enclosure lid clearance is tight; a 100 mm deep enclosure leaves roughly 21.5 mm for wiring behind the breaker. Single terminal per pole top and bottom keeps daisy-chaining straightforward. IP20 finger-safe terminals suit enclosed distribution boards; not rated for wet or dusty environments.","metaTitle":"Schneider Electric A9K23616 Acti9 iK60 MCB, 16A Curve B 1P+N","metaDescription":"Schneider Electric A9K23616 Acti9 iK60N miniature circuit breaker, 16 A rated, curve B, 1P+N, 6 kA breaking capacity per EN/IEC 60898-1. Current production. Sourced to order agains","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"85 mm","Standards":"EN/IEC 60898-1","Curve code":"B","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iK60","Mounting mode":"Clip-on","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"ON/OFF indication","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"2 conforming to EN/IEC 60898-1","Breaking capacity":"6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iK60N","Network frequency":"50/60 Hz","Poles description":"1P + N","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"16 A at 30 °C","Overvoltage category":"III","Trip unit technology":"Thermal-magnetic","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Single terminal (top or bottom) 1...25 mm² rigid","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"3...5 x In","Earth-leakage protection":"Without","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1","Contact position indicator":"No","Locking options description":"Padlocking device","[Ui] rated insulation voltage":"440 V AC 50/60 Hz conforming to EN/IEC 60898-1","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"6000 A 100 % conforming to EN/IEC 60898-1 - 230 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"4 kV conforming to EN/IEC 60898-1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9K23616/miniature-circuit-breaker-ik60n-1p-+-n-16-a-b-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9K23616/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for A9K23616?","answer":"Submit an RFQ through the storefront; the part is sourced to order through independent distribution, and availability with current pricing is confirmed at quote time."},{"question":"What is the closest alternative to A9K23616 in the Acti9 range?","answer":"Within the same Acti9 iK60 series, the main alternative is a different curve or rating — for example, a curve C version of the same 16 A 1P+N breaker (order code A9K23617) if the load has higher inrush. The footprint, breaking capacity, and DIN-rail fit are identical; only the magnetic threshold changes."},{"question":"What is A9K23616's depth?","answer":"78.5 mm from the DIN-rail mounting face to the front of the toggle."},{"question":"What compliance documentation does Schneider provide for A9K23616?","answer":"The breaker is certified to EN/IEC 60898-1, carries IP20 per IEC 60529, and is rated for pollution degree 2 and overvoltage category III. Standard Schneider documentation includes the declaration of performance and CE declaration of conformity; RoHS and REACH compliance data is available on request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9K23616","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9K23616 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}