{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9K23663","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9K23663","canonicalUrl":"https://aoctrl.com/schneider/A9K23663","factsUrl":"https://aoctrl.com/api/mcp/products/A9K23663","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iK60N miniature circuit breaker, A9K23663, 1P+N, 63 A, curve B, 6 kA breaking capacity, thermal-magnetic trip, DIN-rail mount.","salesMarkdown":"The Schneider Electric A9K23663 is a 1P+N miniature circuit breaker from the Acti9 iK60N series, rated 63 A at 30 °C with a B-curve trip characteristic (magnetic trip between 3 and 5 times In). Breaking capacity is 6000 A Icn at 230 V AC, 50/60 Hz, per EN/IEC 60898-1 — enough for most final-distribution fault levels, but check your prospective short-circuit current before committing the BOM line. Rated 63 A at 30 °C ambient. That is the continuous current the thermal element carries without tripping. Above 30 °C you derate per the standard curve — a panel running at 40 °C knocks about 5 % off that figure. The B curve trips the magnetic element at 3–5× In (189–315 A), which suits resistive and general-purpose loads; it avoids nuisance trips on modest inrush that a C curve would ignore. The 440 V rated insulation voltage (Ui) covers 230/400 V networks with margin. Width is 36 mm (4 × 9 mm pitches), so it occupies two standard module spaces. Neutral is on the left, which matters when laying out a multi-row panel — keep the busbar orientation consistent. Terminals accept 1 to 35 mm² rigid wire; strip 14 mm and torque to 3.5 N.m. The single terminal per pole (top and bottom) is straightforward for a panel wireman — no piggyback lugs, just one conductor per side. IP20 finger-safe only — this breaker lives inside a closed panel, not on the surface.","metaTitle":"A9K23663 Acti9 iK60N MCB, 1P+N, 63 A, Curve B, 6 kA","metaDescription":"Schneider Electric A9K23663 Acti9 iK60N miniature circuit breaker, 1P+N, 63 A rated current, curve B, 6 kA breaking capacity, EN/IEC 60898-1. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Color":"White","Depth":"78.5 mm","Width":"36 mm","Height":"85 mm","IP Rating":"IP20","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"2 conforming to EN/IEC 60898-1","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Breaking Capacity":"6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1","Insulation Voltage Ui":"440 V AC 50/60 Hz conforming to EN/IEC 60898-1","Temp Operating Max":"60 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Electrical Life Cycles":"10000 cycles","Mechanical Life Cycles":"20000 cycles","Main Product Or Component Type":"Miniature circuit-breaker","Ambient Air Temperature Operation":"-25...60 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d2dbb863582e7e28a3d79b4856760bb1.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9K23663/miniature-circuit-breaker-ik60n-1p-+-n-63-a-b-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9K23663/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9K23663","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9K23663 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}