{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9K24113","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9K24113","canonicalUrl":"https://aoctrl.com/schneider/A9K24113","factsUrl":"https://aoctrl.com/api/mcp/products/A9K24113","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iK60N miniature circuit-breaker, A9K24113, 1P, 13 A, C-curve, 6000 A Icn at 230 V AC, thermal-magnetic trip, clip-on DIN rail mount, IP20.","salesMarkdown":"The Schneider Electric A9K24113 is an Acti9 iK60N miniature circuit-breaker (MCB) rated 13 A at 30 °C, single-pole, with a C-curve trip characteristic (magnetic tripping between 5 and 10 times In). It breaks 6000 A Icn at 230 V AC 50/60 Hz, conforming to EN/IEC 60898-1 — the standard for overcurrent protection in residential and commercial distribution boards. The 440 V rated insulation voltage (Ui) confirms the MCB is rated for the voltage stress across its open contacts in a 230/400 V system. ## Panel integration The tunnel-type terminals accept 1–25 mm² rigid or 1–16 mm² flexible cable; strip 14 mm and torque to 2 N.m. The toggle actuator provides ON/OFF indication and accepts a padlocking device for lockout/tagout. IP20 finger protection is standard for enclosed panels.","metaTitle":"Schneider Electric A9K24113 Acti9 iK60 MCB, 13 A, 1P, C-Curv","metaDescription":"Schneider Electric A9K24113 Acti9 iK60N miniature circuit-breaker, 13 A rated, 1-pole, C-curve, 6 kA breaking capacity per EN/IEC 60898-1. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"85 mm","Standards":"EN/IEC 60898-1","Curve code":"C","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iK60","Mounting mode":"Clip-on","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"ON/OFF indication","Mounting support":"DIN rail","Pollution degree":"2 conforming to EN/IEC 60898-1","Breaking capacity":"6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iK60N","Network frequency":"50/60 Hz","Poles description":"1P","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"13 A at 30 °C","Overvoltage category":"III","Trip unit technology":"Thermal-magnetic","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Tunnel type terminal (top or bottom) 1...25 mm² rigid Tunnel type terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Without","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1","Contact position indicator":"No","Locking options description":"Padlocking device","[Ui] rated insulation voltage":"440 V AC 50/60 Hz conforming to EN/IEC 60898-1","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"6000 A 100 % conforming to EN/IEC 60898-1 - 230 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"4 kV conforming to EN/IEC 60898-1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9K24113/miniature-circuit-breaker-mcb-acti9-ik60n-1p-13a-c-curve-6000a-iec-en-608981/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9K24113/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9K24113 and get a price?","answer":"The A9K24113 is available to order through independent distribution channels. Submit an RFQ for current pricing and availability — both are confirmed at quote time."},{"question":"What is the breaking capacity of A9K24113?","answer":"The A9K24113 has a breaking capacity of 6000 A Icn at 230 V AC 50/60 Hz, conforming to EN/IEC 60898-1."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9K24113","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9K24113 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}