{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9K24202","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9K24202","canonicalUrl":"https://aoctrl.com/schneider/A9K24202","factsUrl":"https://aoctrl.com/api/mcp/products/A9K24202","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iK60N, miniature circuit breaker, 2A, C-curve, 2P, 6kA Icn at 400V AC, EN/IEC 60898-1, clip-on DIN rail, thermal-magnetic trip, IP20.","salesMarkdown":"The A9K24202 is a 2-pole Acti9 iK60N miniature circuit breaker rated 2 A at 30 °C with a C-curve magnetic trip (5 to 10 × In). The thermal-magnetic trip unit handles both sustained overloads (bimetal strip) and short-circuit events (solenoid). Rated insulation voltage is 440 V AC, so it's fine on 230/400 V three-phase panels. The C-curve is the default for general-purpose distribution — lighting, socket outlets, small motor loads — where inrush is moderate. For a 2 A rating that means motor starting currents up to roughly 20 A peak before the magnetic trip clears it. Clip-on mount to standard 35 mm DIN rail. Width is 36 mm (4 × 9 mm pitches), depth 78.5 mm, height 85 mm. Tunnel terminals accept 1 to 25 mm² rigid or 1 to 16 mm² flexible cable; tighten to 2 N·m. Strip length 14 mm. The ON/OFF toggle provides local indication; padlocking device available for lockout/tagout. Pollution degree 2 (non-conductive, occasional condensation) and overvoltage category II cover normal residential and commercial panel conditions. Limitation class 3 per that standard — the let-through energy is low enough to protect downstream equipment in most fault scenarios. Suitability for isolation confirmed, meaning you can safely use it as a disconnection point with the toggle off.","metaTitle":"Schneider Electric A9K24202 Acti9 iK60N MCB, 2A C-Curve 2P 6","metaDescription":"Schneider Electric A9K24202 Acti9 iK60N miniature circuit breaker, 2A rated, C-curve, 2-pole, 6kA breaking capacity at 400V AC. EN/IEC 60898-1. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"85 mm","Standards":"EN/IEC 60898-1","Curve code":"C","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iK60","Mounting mode":"Clip-on","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"ON/OFF indication","Mounting support":"DIN rail","Pollution degree":"2 conforming to EN/IEC 60898-1","Breaking capacity":"6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iK60N","Network frequency":"50/60 Hz","Poles description":"2P","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"2 A at 30 °C","Overvoltage category":"II","Trip unit technology":"Thermal-magnetic","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Tunnel type terminal (top or bottom) 1...25 mm² rigid Tunnel type terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Without","Number of protected poles":"2","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1","Contact position indicator":"No","Locking options description":"Padlocking device","[Ui] rated insulation voltage":"440 V AC 50/60 Hz conforming to EN/IEC 60898-1","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"6000 A 100 % conforming to EN/IEC 60898-1 - 400 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"4 kV conforming to EN/IEC 60898-1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$17.13","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6326464d6823472d8c7feeef02af8b05.pdf","sourceUrl":"https://www.se.com/in/en/product/A9K24202/miniature-circuit-breaker-mcb-acti9-ik60n-2p-2a-c-curve-6000a-iec-en-608981/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9K24202/alternatives.json"},"ai":{"faq":[{"question":"How do I get pricing and availability for A9K24202?","answer":"Pricing and availability are confirmed at quote time against an RFQ. Submit a request through the distributor channel; the part is sourced to order and current stock levels are checked on your inquiry."},{"question":"What is the breaking capacity of A9K24202?","answer":"The breaking capacity is 6000 A Icn at 400 V AC, 50/60 Hz, conforming to EN/IEC 60898-1. That is the standard domestic/commercial fault-interruption rating for this class of MCB."},{"question":"What is the closest alternative to A9K24202 in the Acti9 family?","answer":"Within the Acti9 iK60 range, the closest sibling is the single-pole version (1P) at the same 2 A C-curve rating. The 2-pole A9K24202 is the one you want when you need both line and neutral protection on a single module width of 36 mm."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9K24202","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9K24202 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}