{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9K24602","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9K24602","canonicalUrl":"https://aoctrl.com/schneider/A9K24602","factsUrl":"https://aoctrl.com/api/mcp/products/A9K24602","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iK60 series, miniature circuit-breaker A9K24602, 1P+N, 2 A, C-curve, 6 kA at 230 V AC, DIN-rail clip-on.","salesMarkdown":"Schneider Electric A9K24602 is an Acti9 iK60N miniature circuit-breaker rated 2 A at 30 °C, 1P+N, with a C-curve trip characteristic (magnetic tripping between 5 and 10 x In). It breaks 6000 A Icn at 230 V AC, 50/60 Hz, per EN/IEC 60898-1. That 6 kA rating covers common residential and light commercial panel faults — enough for a distribution sub-board where the upstream device limits the prospective short-circuit current. Tunnel terminals top and bottom accept 1 to 25 mm² rigid or 1 to 16 mm² flexible; strip 14 mm and torque to 2 N·m. IP20 rated, so it stays inside a closed panel or enclosure.","metaTitle":"A9K24602 Acti9 iK60 MCB, 2A 1P+N C-curve, 6kA","metaDescription":"A9K24602 Acti9 iK60N miniature circuit-breaker, 2 A rated, 1P+N, C-curve, 6 kA breaking capacity. Active production. EN/IEC 60898-1. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"85 mm","Standards":"EN/IEC 60898-1","Curve code":"C","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iK60","Mounting mode":"Clip-on","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"ON/OFF indication","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"2 conforming to EN/IEC 60898-1","Breaking capacity":"6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iK60N","Network frequency":"50/60 Hz","Poles description":"1P + N","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"2 A at 30 °C","Overvoltage category":"II","Trip unit technology":"Thermal-magnetic","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Tunnel type terminal (top or bottom) 1...25 mm² rigid Tunnel type terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Without","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1","Contact position indicator":"No","Locking options description":"Padlocking device","[Ui] rated insulation voltage":"440 V AC 50/60 Hz conforming to EN/IEC 60898-1","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"6000 A 100 % conforming to EN/IEC 60898-1 - 230 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"4 kV conforming to EN/IEC 60898-1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9K24602/miniature-circuit-breaker-mcb-acti9-ik60n-1p+n-2a-c-curve-6000a-iec-en-608981/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9K24602/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for A9K24602?","answer":"Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution channels."},{"question":"What is A9K24602's breaking capacity?","answer":"It is rated 6000 A Icn at 230 V AC, 50/60 Hz, conforming to EN/IEC 60898-1."},{"question":"What compliance standards does A9K24602 meet?","answer":"It conforms to EN/IEC 60898-1, carries pollution degree 2 and overvoltage category II, and is rated for isolation per the same standard."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9K24602","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9K24602 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}