{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9K24613","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9K24613","canonicalUrl":"https://aoctrl.com/schneider/A9K24613","factsUrl":"https://aoctrl.com/api/mcp/products/A9K24613","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iK60N, miniature circuit breaker, 1P+N, 13 A, C-curve, 6 kA Icn at 230 V AC, EN/IEC 60898-1, DIN rail clip-on.","salesMarkdown":"The Schneider Electric A9K24613 is a 1P+N miniature circuit breaker from the Acti9 iK60N series, rated 13 A at 30 °C with a C-curve magnetic trip (5...10 x In). The 1P+N configuration switches the phase and breaks the neutral, but only the phase is protected (one protected pole). The neutral is switched but not monitored for overload — standard for single-phase final circuits where the neutral is not expected to carry imbalance current. Clip-on mounting to DIN rail (35 mm per EN 60715). Depth is 78.5 mm, height 85 mm. Tunnel terminals accept 1...25 mm² rigid or 1...16 mm² flexible copper; tighten to 2 N.m. Strip 14 mm of insulation. Pollution degree 2 (non-conductive dust, occasional condensation) matches typical indoor panel conditions. Overvoltage category II applies, so it is intended for fixed-installation socket and lighting circuits, not for incoming mains or utility metering.","metaTitle":"Schneider Electric A9K24613 Acti9 iK60N MCB, 1P+N, 13 A, C-C","metaDescription":"Schneider Electric A9K24613 Acti9 iK60N miniature circuit breaker. 1P+N, 13 A rated current, C-curve, 6 kA breaking capacity at 230 V AC. EN/IEC 60898-1. DIN rail clip-on. Sourced","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Color":"White","Depth":"78.5 mm","Width":"36 mm","Height":"85 mm","IP Rating":"IP20","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"2 conforming to EN/IEC 60898-1","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Breaking Capacity":"6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1","Insulation Voltage Ui":"440 V AC 50/60 Hz conforming to EN/IEC 60898-1","Temp Operating Max":"60 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Electrical Life Cycles":"10000 cycles","Mechanical Life Cycles":"20000 cycles","Main Product Or Component Type":"Miniature circuit-breaker","Ambient Air Temperature Operation":"-25...60 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/25f7da911169d3a371851f69277ba333.pdf","sourceUrl":"https://www.se.com/in/en/product/A9K24613/miniature-circuitbreaker-acti9-ik60n-1p+n-13-a-c-curve-6000-a-iec-608981/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9K24613/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9K24613","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9K24613 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}