{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9K24732","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9K24732","canonicalUrl":"https://aoctrl.com/schneider/A9K24732","factsUrl":"https://aoctrl.com/api/mcp/products/A9K24732","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iK60N miniature circuit-breaker, A9K24732, 3P+N, 32 A rated, C curve, 6000 A breaking capacity at 400 V AC, thermal-magnetic trip, DIN rail clip-on, white.","salesMarkdown":"The A9K24732 is a Schneider Electric Acti9 iK60N miniature circuit-breaker — a thermal-magnetic MCB rated 32 A at 30 °C, with a C curve (magnetic trip between 5 and 10 times In) and a 6000 A breaking capacity at 400 V AC, 50/60 Hz, conforming to EN/IEC 60898-1. This is a 3P+N unit — three protected poles plus a switched neutral pole on the left. The neutral pole is not thermally protected; it switches with the phase poles, so it's suited for distribution schemes where the neutral is solidly bonded upstream and only needs disconnection for isolation. The part carries isolation suitability per EN/IEC 60898-1, meaning it can be used as a disconnecting means for the downstream circuit when padlocked off. The 9 mm pitch count of 8 means the breaker occupies 8 modules (72 mm width) on the rail — plan your enclosure fill accordingly. Height is 85 mm, depth 78.5 mm, so it fits most distribution boards without crowding the gland plate. Tunnel-type terminals accept 1 to 25 mm² rigid or 1 to 16 mm² flexible cable; strip 14 mm and tighten to 2 N.m. IP20 finger-safe front, but the terminals are live when wired — standard for distribution MCBs.","metaTitle":"A9K24732 Acti9 iK60N Miniature Circuit-Breaker, 32 A, C Curv","metaDescription":"Schneider Electric A9K24732 Acti9 iK60N MCB, 32 A rated, C curve, 6000 A breaking capacity at 400 V AC, 3P+N, DIN rail mount, EN/IEC 60898-1. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Circuit Breaker Accessories"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"72 mm","Colour":"White","Height":"85 mm","Standards":"EN/IEC 60898-1","Curve code":"C","9 Mm Pitches":"8","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iK60","Mounting mode":"Clip-on","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"ON/OFF indication","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"2 conforming to EN/IEC 60898-1","Breaking capacity":"6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iK60N","Network frequency":"50/60 Hz","Poles description":"3P + N","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"32 A at 30 °C","Overvoltage category":"III","Trip unit technology":"Thermal-magnetic","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Tunnel type terminal (top or bottom) 1...25 mm² rigid Tunnel type terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Without","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1","Locking options description":"Padlocking device","[Ui] rated insulation voltage":"440 V AC 50/60 Hz conforming to EN/IEC 60898-1","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"6000 A 100 % conforming to EN/IEC 60898-1 - 400 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"4 kV conforming to EN/IEC 60898-1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9K24732/miniature-circuit-breaker-mcb-acti9-ik60n-3p+n-32a-c-curve-6000a-iec-en-608981/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9K24732/alternatives.json"},"ai":{"faq":[{"question":"What is A9K24732's listed depth?","answer":"The depth is 78.5 mm. That fits standard distribution enclosures without crowding the gland plate."},{"question":"What is A9K24732's listed range?","answer":"It belongs to the Schneider Electric Acti9 range, specifically the iK60N series of miniature circuit-breakers."},{"question":"What compliance documentation does this brand provide for A9K24732?","answer":"The breaker is certified to EN/IEC 60898-1. It carries a limitation class 3 rating and pollution degree 2 per that standard. For specific RoHS, REACH, or UL documentation, request the manufacturer's declaration at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9K24732","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9K24732 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}