{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9KF71106","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9KF71106","canonicalUrl":"https://aoctrl.com/schneider/A9KF71106","factsUrl":"https://aoctrl.com/api/mcp/products/A9KF71106","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 K60, A9KF71106, miniature circuit breaker, 1P, 6 A, C-curve, 10 kA Icn at 240 V AC, DIN rail mount.","salesMarkdown":"The Schneider Electric A9KF71106 is a 1-pole Acti9 K60 miniature circuit breaker rated 6 A with a C-curve, meaning magnetic tripping occurs between 5 and 10 times the rated current (30–60 A). Snaps onto a standard DIN rail (35 mm) and occupies 2 x 9 mm pitches (18 mm wide) — one modular unit for a 1P breaker. Tunnel terminals accept 1–25 mm² rigid or 1–16 mm² flexible copper; strip length is 14 mm, torque to 2 N·m. Height is 81 mm, depth 70 mm — fits standard consumer unit and sub-distribution board cutouts. Limitation class 3 (energy-limiting) per the same standard — it restricts let-through energy enough to protect downstream wiring and connected equipment during a short-circuit. Pollution degree 2 (non-conductive pollution only, occasional condensation), overvoltage category II (appliance / plug-connected loads). Operating altitude is 0–2000 m without derating.","metaTitle":"Schneider Electric A9KF71106 Acti9 K60 MCB, 6 A C-Curve 1P 1","metaDescription":"Schneider Electric A9KF71106 Acti9 K60 miniature circuit breaker, 6 A rated current, C-curve, 1-pole, 10 kA breaking capacity at 240 V AC. EN/IEC 60898-1. Sourced to order against","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"70 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"81 mm","Standards":"EN/IEC 60898-1","Curve code":"C","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC","Product name":"Acti9 K60","Mounting mode":"Fixed","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Without","Mounting support":"DIN rail","Pollution degree":"2","Breaking capacity":"10000 A Icn at 240 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"K60H","Network frequency":"50/60 Hz","Poles description":"1P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","Operating altitude":"0...2000 m","[In] rated current":"6 A","Overvoltage category":"II","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Tunnel type terminals (downstream) 1...25 mm² rigid Tunnel type terminals (upstream) 1...25 mm² rigid Tunnel type terminals (downstream) 1...16 mm² flexible Tunnel type terminals (upstream) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Without","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1","Contact position indicator":"No","[Ui] rated insulation voltage":"500 V AC 50/60 Hz","Ambient air temperature for storage":"-25...85 °C","Ambient air temperature for operation":"-5...55 °C","[Ics] rated service breaking capacity":"7500 A 75 % conforming to EN/IEC 60898-1 - 240 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"4 kV","Comb busbar and distribution block compatibility":"Downstream: biconnect"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9KF71106/acti9-k60h-1p-6-a-c-curve-10000-a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9KF71106/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of A9KF71106?","answer":"The A9KF71106 has a rated breaking capacity (Icn) of 10,000 A at 240 V AC, 50/60 Hz, conforming to EN/IEC 60898-1."},{"question":"What does the C-curve on A9KF71106 mean?","answer":"The C-curve means the magnetic trip operates between 5 and 10 times the rated current — for this 6 A breaker, that's 30–60 A. It is the standard curve for general-purpose distribution circuits with moderate inrush."},{"question":"Where can I buy A9KF71106 and how is it quoted?","answer":"A9KF71106 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or lead-time figure is carried on this page."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9KF71106","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9KF71106 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}