{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9KF71210BQ","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9KF71210BQ","canonicalUrl":"https://aoctrl.com/schneider/A9KF71210BQ","factsUrl":"https://aoctrl.com/api/mcp/products/A9KF71210BQ","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 K60, miniature circuit-breaker, A9KF71210BQ, 10 A, C curve, 2P, 10 kA Icn at 415 V AC, DIN-rail mount.","salesMarkdown":"The Schneider Electric A9KF71210BQ is an Acti9 K60 miniature circuit-breaker rated 10 A with a C curve, 2 poles, and a 10 kA Icn breaking capacity at 415 V AC conforming to EN/IEC 60898-1. The C curve (magnetic trip 5–10 × In) means it handles moderate inrush — typical for general-purpose distribution, lighting, and small motor loads — without nuisance tripping. The thermal-magnetic trip unit gives you both overload protection (bimetal strip) and short-circuit protection (solenoid) in one 36 mm wide, 2-pole package that snaps onto a DIN rail. Rated altitude 0–2000 m and pollution degree 2 cover the vast majority of indoor panel installations. The IP20 finger-safe terminals are fine inside a closed enclosure; if you're mounting this in a standalone box exposed to dust or moisture, the enclosure itself needs the IP rating. The 36 mm width occupies 4 modules of 9 mm pitch — account for that in your rail fill calculation. Terminals accept 1–25 mm² rigid or 1–16 mm² flexible copper; strip length 14 mm, tighten to 2 N·m. The toggle actuator gives clear visual indication of tripped vs on/off state. No earth-leakage protection built in — if you need that, add a separate RCD downstream.","metaTitle":"Schneider Electric A9KF71210BQ Acti9 K60 MCB, 10 A, C Curve,","metaDescription":"Schneider Electric A9KF71210BQ Acti9 K60 miniature circuit-breaker, 10 A rated current, C curve, 2 poles, 10 kA breaking capacity at 415 V AC, EN/IEC 60898-1. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"70 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"81 mm","Standards":"EN/IEC 60898-1","Curve code":"C","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 K60","Mounting mode":"Fixed","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Without","Mounting support":"DIN rail","Pollution degree":"2","Quantity per set":"Set of 6","Breaking capacity":"10000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"K60H","Network frequency":"50/60 Hz","Poles description":"2P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","Operating altitude":"0...2000 m","[In] rated current":"10 A","Overvoltage category":"II","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Tunnel type terminals (downstream) 1...25 mm² rigid Tunnel type terminals (upstream) 1...25 mm² rigid Tunnel type terminals (downstream) 1...16 mm² flexible Tunnel type terminals (upstream) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Without","Number of protected poles":"2","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1","Contact position indicator":"No","[Ui] rated insulation voltage":"500 V AC 50/60 Hz","Ambient air temperature for storage":"-25...85 °C","Ambient air temperature for operation":"-5...55 °C","[Ics] rated service breaking capacity":"7500 A 75 % conforming to EN/IEC 60898-1 - 415 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"4 kV","Comb busbar and distribution block compatibility":"Downstream: biconnect"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9KF71210BQ/acti-9-k60h-2p-10-a-c-curve-10-ka-set-of-6/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9KF71210BQ/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9KF71210BQ and what is the lead time?","answer":"A9KF71210BQ is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for the real ETA."},{"question":"What is A9KF71210BQ's breaking capacity?","answer":"It has a 10 kA Icn breaking capacity at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1."},{"question":"What does the C curve mean on this MCB?","answer":"The C curve means the magnetic trip operates at 5–10 times the rated current (In). This is suited for circuits with moderate inrush, like general distribution, lighting, and small motors."},{"question":"What compliance documentation does this brand provide for A9KF71210BQ?","answer":"The part is certified to EN/IEC 60898-1 and carries tropicalisation class 2 per IEC 60068-1. For RoHS, REACH, and UL documentation, refer to the manufacturer's compliance portal or request the declaration with your RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9KF71210BQ","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9KF71210BQ when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}