{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9KR11463BQ","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9KR11463BQ","canonicalUrl":"https://aoctrl.com/schneider/A9KR11463BQ","factsUrl":"https://aoctrl.com/api/mcp/products/A9KR11463BQ","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 ID K, residual current circuit breaker (RCCB), 4P, 63 A, 30 mA, 380-415 V AC, DIN rail clip-on, IP20/IP40.","salesMarkdown":"The Schneider Electric A9KR11463BQ is a 4-pole residual current circuit breaker (RCCB) from the Acti9 ID K series, rated 63 A continuous current with 30 mA earth-leakage sensitivity. The 30 mA sensitivity is instantaneous (no time delay), so it trips on the first half-cycle of a ground fault — this is the standard for personnel protection in IEC 61008-1 circuits. The insulation voltage (Ui) is 440 V AC, so the internal clearances and creepage are sized for a 440 V system even though the operational voltage is capped at 415 V. That headroom matters when the supply rides high or when the RCCB is used in a corner-grounded delta configuration (rare, but the rating covers it). Terminals accept rigid conductors up to 35 mm² or flexible up to 25 mm², with a stripping length of 14 mm and tightening torque of 3.5 N.m. The biconnect design allows top or bottom feed — useful when daisy-chaining through the same terminal without a separate busbar. IP20 on the body, IP40 inside a modular enclosure, so it needs a cabinet or distribution board to meet washdown or dust ingress requirements. The Acti9 ID K family is a standard line, not a niche or phased-out variant. The A9KR11463BQ is certified to IS 12640-1, EN/IEC 61008-1, and EN/IEC 61008-2-1. That covers the Indian standard and the European harmonized standard for residual current operated circuit-breakers without integral overcurrent protection. Pollution degree 2 (non-conductive pollution that becomes conductive only when condensation occurs) is the typical rating for enclosed distribution boards.","metaTitle":"Schneider Electric A9KR11463BQ Acti9 ID K RCCB, 63 A, 30 mA,","metaDescription":"Schneider Electric A9KR11463BQ Acti9 ID K RCCB, 63 A rated current, 30 mA earth-leakage sensitivity, 4 poles, 380-415 V AC, DIN rail mount. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"68 mm","Range":"Acti9","Width":"72 mm","Colour":"White","Height":"81 mm","Standards":"IS 12640-1 EN/IEC 61008-1 EN/IEC 61008-2-1","9 Mm Pitches":"8","Control type":"Toggle","Network type":"AC","Product name":"Acti9 ID K","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"2","Quantity per set":"Set of 3","Device short name":"ID K","Network frequency":"50 Hz","Poles description":"4P","Relative humidity":"95 % at 55 °C","Tightening torque":"3.5 N.m top or bottom","[In] rated current":"63 A","Electrical durability":"AC-1: 4000 cycles","Mechanical durability":"5000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Biconnect top or bottom 1...35 mm² rigid Biconnect top or bottom 1...25 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Device location in system":"Group incomer","Earth-leakage sensitivity":"30 mA","Product or component type":"Residual current circuit breaker (RCCB)","Contact position indicator":"No","Electromagnetic compatibility":"8/20 µs impulse withstand, 200 A conforming to EN/IEC 61008-1","[Ui] rated insulation voltage":"440 V AC 50 Hz","Earth-leakage protection class":"Type AC","[Ue] rated operational voltage":"380...415 V AC 50 Hz","Rated breaking and making capacity":"Idm 630 A Im 630 A","Ambient air temperature for storage":"-25...85 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-5...55 °C","[Uimp] rated impulse withstand voltage":"4 kV","Rated conditional short-circuit current":"GL63: Inc 4.5 kA K60: Inc 6 kA"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9KR11463BQ/acti-9-id-k-rccb-4p-63a-30ma-type-ac-set-of-3/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9KR11463BQ/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9KR11463BQ and what is the lead time?","answer":"The A9KR11463BQ is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the closest alternative to A9KR11463BQ in the same family?","answer":"The A9KR11463BQ is a standard Acti9 ID K RCCB. Within the same family, other order codes differ by rated current and sensitivity; no pin-compatible direct replacement is listed as an official successor."},{"question":"What is A9KR11463BQ's depth?","answer":"The depth is 68 mm."},{"question":"What compliance documentation does Schneider provide for A9KR11463BQ?","answer":"The device is certified to IS 12640-1, EN/IEC 61008-1, and EN/IEC 61008-2-1. It also meets tropicalization class 2 per IEC 60068-1 and pollution degree 2."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9KR11463BQ","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9KR11463BQ when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}