{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9L15593","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9L15593","canonicalUrl":"https://aoctrl.com/schneider/A9L15593","factsUrl":"https://aoctrl.com/api/mcp/products/A9L15593","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iPF Type 2 surge arrester, 4 poles, 340 V, 20 kA per mode, clip-on DIN rail, white (RAL 9003).","salesMarkdown":"The Schneider Electric A9L15593 is a Type 2 surge arrester from the Acti9 iPF range, designed for distribution networks in small commercial installations. It uses MOV technology to clamp surge voltages on a 230/400 V AC TN-C system, with a nominal discharge current of 5 kA per mode and a maximum of 20 kA per mode (L/PE and N/PE). The total discharge capacity reaches 80 kA across all four poles. It clips onto a DIN rail (snap-on mounting) and occupies 8 modules of 9 mm pitch — that's 72 mm of panel width, with a depth of 69 mm and height of 81.4 mm. The tunnel-type terminals accept 2.5 to 35 mm² conductors, torqued to 2.5 N·m. If you need a drop-in replacement, the closest functional peer in the Acti9 iPF family shares the same Type 2 MOV design and 4-pole form factor; the key difference to verify is the maximum continuous operating voltage (Uc) and the protection level (Up) for your specific earthing system. The 340 V Uc (maximum continuous operating voltage) means this arrester can sit on a 230/400 V TN-C system without clipping the line voltage during normal operation. The protection level Up is under 1.1 kV — that's the let-through voltage the downstream equipment sees during a surge event. For sensitive electronics, verify that 1.1 kV is within the impulse withstand of your load side. The IK03 impact rating (per IEC 62262) means the enclosure withstands 0.35 J — enough for accidental tool contact during panel work, but not a heavy blow. The operating temperature range is -25 to 60 °C, with storage from -40 to 85 °C; the relative humidity limit of 5 to 90 % covers most indoor panel environments.","metaTitle":"Schneider Electric A9L15593 Acti9 iPF Surge Arrester, Type 2","metaDescription":"Schneider Electric A9L15593 Acti9 iPF Type 2 surge arrester, 4 poles, 340V, 20 kA per mode. Obsolete — sourced to order against RFQ. Clip-on DIN rail.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Color":"White (RAL 9003)","Depth":"69 mm","Width":"72 mm","Height":"81.4 mm","Voltage":"230/400 V AC (+/- 10 %) at 50/60 Hz","Application":"Distribution","Product Status":"Active","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Temp Operating Max":"60 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Main Product Or Component Type":"Surge arrester","Ambient Air Temperature Operation":"-25...60 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/bc02b8ef680f3d1483698099d9f325bb.pdf","sourceUrl":"https://www.se.com/za/en/product/A9L15593/ipf20-modular-surge-arrester-4-poles-340v/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9L15593/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9L15593","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9L15593 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}