{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9L16597","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9L16597","canonicalUrl":"https://aoctrl.com/schneider/A9L16597","factsUrl":"https://aoctrl.com/api/mcp/products/A9L16597","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iPRD40r, Type 2 surge arrester, 4P, 460 V, 40 kA max discharge, with remote signalling, white (RAL 9003).","salesMarkdown":"The Schneider Electric A9L16597 is an Acti9 iPRD40r modular surge arrester — a Type 2 MOV-based unit rated for 230/400 V AC distribution networks in IT earthing systems. It carries a maximum discharge current of 40 kA per pole (common mode L/PE and N/PE) and a nominal discharge current of 15 kA. The 4-pole configuration with remote signalling (1 C/O contact rated 0.25 A / 250 V AC) makes it suitable for panel applications where remote monitoring of arrester status is required. Clip-on DIN rail mounting (72 mm wide, 81 mm tall, 69 mm deep) fits standard panel enclosures. The tunnel-type terminals accept 2.5 to 35 mm² conductors, with a tightening torque of 2.5 N·m. The Type 2 classification per EN/IEC 61643-11 means it is designed for the main distribution board to limit overvoltages from switching transients and indirect lightning — not for direct-strike primary protection. The 460 V Uc (maximum continuous operating voltage) matches 230/400 V AC networks with typical tolerances. Operating temperature range is -25 to +60 °C, storage -40 to +85 °C, with 5 to 90 % relative humidity. ## Associated circuit breaker requirement The iPRD40r requires an associated circuit breaker for overcurrent protection and disconnection. Schneider specifies the iC60N, iC60H, or iC60L at 40 A curve C, with Icu ratings of 10 kA, 15 kA, or 25 kA respectively. This is a mandatory pairing — the arrester alone does not provide overcurrent protection.","metaTitle":"Schneider Electric A9L16597 Acti9 iPRD40r Surge Arrester, 4P","metaDescription":"Schneider Electric A9L16597 Acti9 iPRD40r Type 2 surge arrester, 4 poles, 460 V, 40 kA max discharge. Obsolete — sourced to order against RFQ via independent distribution.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Color":"White (RAL 9003)","Depth":"69 mm","Width":"72 mm","Height":"81 mm","Voltage":"230/400 V AC (+/- 10 %) at 50/60 Hz","Application":"Distribution","Product Status":"Active","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Temp Operating Max":"60 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Ambient Air Temperature Operation":"-25...60 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/vn/en/product/A9L16597/iprd-40r-modular-surge-arrester-4-poles-460-v-with-remote-transfer/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9L16597/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9L16597","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9L16597 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}