{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9L65101","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9L65101","canonicalUrl":"https://aoctrl.com/schneider/A9L65101","factsUrl":"https://aoctrl.com/api/mcp/products/A9L65101","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iPRD65r, Type 2 surge arrester, 1P, 350 V, 65 kA max discharge, with remote signalling, clip-on DIN rail mount.","salesMarkdown":"The A9L65101: The Type 2 classification (per EN 61643-11:2012 and IEC 61643-11:2011) means this unit is designed for installation on sub-distribution boards to clamp induced surge voltages from switching or indirect lightning strikes — it is not a primary service entrance protector (Type 1). With a maximum continuous operating voltage Uc of 350 V (L/PE and N/PE), it is compatible with 230/400 V TN and IT networks where the line-to-neutral voltage stays under 350 V. The temporary overvoltage (Ut) withstand of 337 V L/N for 5 seconds and safe failure mode at 1200 V N/PE for 200 ms gives the coordination engineer a defined failure characteristic to design selectivity around. The protection level Up is stated as <1.5 kV (common mode L/PE). That is the voltage the arrester lets through to the protected equipment during a discharge event. For downstream equipment with a rated impulse withstand (Uimp) of 2.5 kV or higher, this provides adequate margin. The 1 SD (1 C/O) remote signalling contact (0.25 A/250 V AC) allows the panel to report a failed cartridge to a PLC or building management system — useful for sites where the arrester is in a locked or inaccessible distribution board. The unit clips onto a DIN rail (EN 60715). Its footprint is 18 mm wide (1 module width) by 85 mm high by 69 mm deep, occupying two 9 mm pitches. The tunnel-type terminals on both top and bottom accept 2.5 to 35 mm² conductors; tightening torque is 2.5 N·m. For a distribution board already populated with Acti9 MCBs, the iPRD65r shares the same form factor and can be mounted directly adjacent, keeping the busbar arrangement clean.","metaTitle":"Schneider Electric A9L65101 Acti9 iPRD65r Type 2 Surge Arres","metaDescription":"Schneider Electric A9L65101 Acti9 iPRD65r Type 2 surge arrester, 1P, 350V, 65 kA max discharge. Active production. Sourced to order against RFQ. EN/IEC 61643-11 certified.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"69 mm","Width":"18 mm","Colour":"White (RAL 9003)","Height":"85 mm","Standards":"EN 61643-11:2012 IEC 61643-11:2011","9 Mm Pitches":"2","Product name":"Acti9 iPRD","Mounting mode":"Clip-on (DIN rail)","Quality labels":"KEMA-KEUR NF","Earthing system":"IT 230 TN-C","lifecycle_stage":"current","Range Of Product":"Acti9","Range of product":"IPRD","Device short name":"iPRD65r","Poles description":"1P","Relative humidity":"5...95 %","Remote signalling":"With","Tightening torque":"2.5 N.m","Compatibility code":"IPRD65r","Device application":"Distribution","Operating altitude":"2000 m","Surge arrester type":"Electrical distribution network","Connections - terminals":"Tunnel type terminal (downside) 2.5...35 mm² Tunnel type terminal (upside) 2.5...35 mm²","IK degree of protection":"IK03 conforming to IEC 62262","Disconnector device type":"Associated circuit breaker IC60N 50 A curve C - Icu 10 kA Associated circuit breaker iC60H 50 A curve C - Icu 15 kA Associated circuit breaker NG125N 50 A curve C - Icu 25 kA Associated circuit breaker NG125H 50 A curve C - Icu 36 kA Associated circuit breaker NG125L 50 A curve C - Icu 50 kA Associated fuse gG 80 A - Icu 50 kA","Maximum discharge current":"Common mode: 65 kA L/PE","Nominal discharge current":"Common mode: 20 kA (L/PE) Common mode: 20 kA (N/PE)","Product or component type":"Surge arrester with pluggable cartridge","Surge arrester class type":"Type 2","Surge arrester technology":"MOV","Signalling circuit voltage":"0.25 A/250 V AC 50/60 Hz","[Ut] temporary overvoltage":"337 V L/N 5 s withstand 1200 V N/PE 200 ms safe failure mode","Signal contacts composition":"1 SD (1 C/O)","[Ipe] Ground residual current":"0.003 mA 0.6 mA","[Ue] rated operational voltage":"230 V AC (+/- 10 %) at 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...60 °C","Maximum [Up] voltage protection level":"Common mode <1.5 kV type 2 L/PE","[Uc] maximum continuous operating voltage":"Common mode: 350 V L/PE Common mode: 350 V N/PE"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$66.41","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/vn/en/product/A9L65101/iprd65r-modular-surge-arrester-1p-350v-with-remote-transfert/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9L65101/alternatives.json"},"ai":{"faq":[{"question":"What is the closest alternative to A9L65101 in the Acti9 iPRD family?","answer":"Within the Acti9 iPRD65r series, the A9L65101 is the 1P variant at 350 V with remote signalling. The 2P (A9L65102) and 3P (A9L65103) variants share the same Type 2, 65 kA max discharge, and MOV technology but add poles for three-phase networks. The choice is driven by the number of protected phases, not by any functional difference in surge performance per pole."},{"question":"How do I get current pricing and availability for A9L65101?","answer":"The A9L65101 is sourced and quoted to order against an RFQ through independent distribution. Submit a request for quote (RFQ) to confirm current pricing and availability; stock levels and lead time are confirmed at the time of quotation."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9L65101","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9L65101 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}