{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9L65201","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9L65201","canonicalUrl":"https://aoctrl.com/schneider/A9L65201","factsUrl":"https://aoctrl.com/api/mcp/products/A9L65201","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iPRD65r, Type 2 surge arrester, 2 poles, 350 V, 65 kA max discharge, with remote signalling, white (RAL 9003).","salesMarkdown":"It carries a 20 kA nominal discharge current per mode (L/PE, N/PE) and a 65 kA maximum discharge current, which means it handles the bulk of lightning-induced surges at the main or sub-distribution board without passing through to downstream equipment. The 230 V AC (+/-10%) rated operational voltage and 350 V maximum continuous operating voltage (Uc) match standard single-phase European mains; the 337 V temporary overvoltage (TOV) withstand for 5 seconds gives it a realistic ride-through for utility switching events before it safely fails. Clip-on DIN rail mounting and a 36 mm width mean it occupies two standard 18 mm modular pitches — check your enclosure's fill factor before the outage window. Tunnel-type terminals accept 2.5 to 35 mm² on both the line and load sides; tighten to 2.5 N·m. The 69 mm depth and 85 mm height leave clearance for wiring ducts and adjacent breakers. Four 9 mm pitches align with the Acti9 comb-busbar system for phase distribution. ## Coordination and disconnector This SPD requires an upstream overcurrent protective device. Schneider lists compatible disconnectors: an IC60N or iC60H (50 A curve C, Icu 10 kA or 15 kA), NG125N/H/L (50 A curve C, Icu 25/36/50 kA), or a gG 80 A fuse (Icu 50 kA). The choice governs the fault-clearing capability at the board — match the Icu to your available fault current. The remote signalling contact (1 C/O, 0.25 A / 250 V AC) lets a PLC or BMS monitor the cartridge status without opening the panel.","metaTitle":"Schneider Electric A9L65201 Acti9 iPRD65r Surge Arrester, 2P","metaDescription":"Schneider Electric A9L65201 Acti9 iPRD65r Type 2 surge arrester, 2P, 350V, 65kA max discharge, with remote signalling. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"69 mm","Width":"36 mm","Colour":"White (RAL 9003)","Height":"85 mm","Standards":"EN 61643-11:2012 IEC 61643-11:2011","9 Mm Pitches":"4","Product name":"Acti9 iPRD","Mounting mode":"Clip-on (DIN rail)","Quality labels":"KEMA-KEUR NF","Earthing system":"TN-C-S","lifecycle_stage":"current","Range Of Product":"Acti9","Range of product":"IPRD","Device short name":"iPRD65r","Poles description":"2P","Relative humidity":"5...95 %","Remote signalling":"With","Tightening torque":"2.5 N.m","Compatibility code":"IPRD65r","Device application":"Distribution","Operating altitude":"2000 m","Surge arrester type":"Electrical distribution network","Connections - terminals":"Tunnel type terminal (downside) 2.5...35 mm² Tunnel type terminal (upside) 2.5...35 mm²","IK degree of protection":"IK03 conforming to IEC 62262","Disconnector device type":"Associated circuit breaker IC60N 50 A curve C - Icu 10 kA Associated circuit breaker iC60H 50 A curve C - Icu 15 kA Associated circuit breaker NG125N 50 A curve C - Icu 25 kA Associated circuit breaker NG125H 50 A curve C - Icu 36 kA Associated circuit breaker NG125L 50 A curve C - Icu 50 kA Associated fuse gG 80 A - Icu 50 kA","Maximum discharge current":"Common mode: 65 kA L/PE Common mode: 65 kA N/PE","Nominal discharge current":"Common mode: 20 kA (L/PE) Common mode: 20 kA (N/PE)","Product or component type":"Surge arrester with pluggable cartridge","Surge arrester class type":"Type 2","Surge arrester technology":"MOV","Signalling circuit voltage":"0.25 A/250 V AC 50/60 Hz","[Ut] temporary overvoltage":"337 V L/N 5 s withstand 1200 V N/PE 200 ms safe failure mode","Signal contacts composition":"1 SD (1 C/O)","[Ipe] Ground residual current":"0.6 mA 0.003 mA","[Ue] rated operational voltage":"230 V AC (+/- 10 %) at 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...60 °C","Maximum [Up] voltage protection level":"Common mode Common mode <1.5 kV type 2 N/PE","[Uc] maximum continuous operating voltage":"Common mode: 350 V L/PE Common mode: 350 V N/PE"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$105.93","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/be/en/product/A9L65201/iprd65r-modular-surge-arrester-2p-350v-with-remote-transfert/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9L65201/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9L65201 and get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What are the key ratings for A9L65201?","answer":"Type 2 surge arrester, 2 poles, 350 V Uc, 20 kA nominal discharge current per mode, 65 kA maximum discharge current, 230 V AC rated operational voltage."},{"question":"What is the depth of A9L65201?","answer":"69 mm. Combined with the 36 mm width and 85 mm height, it fits standard DIN-rail enclosures with clearance for wiring."},{"question":"What compliance documentation does Schneider provide for A9L65201?","answer":"The part is certified to EN 61643-11:2012 and IEC 61643-11:2011, with KEMA-KEUR and NF quality labels. RoHS and REACH declarations are standard for the Acti9 range; request the specific declaration at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9L65201","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9L65201 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}