{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N16202","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N16202","canonicalUrl":"https://aoctrl.com/schneider/A9N16202","factsUrl":"https://aoctrl.com/api/mcp/products/A9N16202","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 xID, residual current circuit breaker (RCCB), 2P, 25 A, 300 mA, Type AC, 230-240 V AC, clip-on DIN rail mount.","salesMarkdown":"The Schneider Electric A9N16202 is an Acti9 xID residual current circuit breaker (RCCB) — a 2-pole, Type AC device rated for 25 A continuous load with 300 mA earth-leakage sensitivity. It operates on a 230-240 V AC, 50 Hz network and clips onto a standard DIN rail. The 25 A rated current (In) sizes the RCCB for a 25 A feeder — common for lighting sub-circuits, general socket groups, or small appliance loads. The 300 mA sensitivity (IΔn) is less sensitive than the 30 mA type used for personal shock protection; it is selected where the priority is fire protection and equipment leakage tolerance, such as on circuits with multiple connected loads that have inherent leakage. For those, a Type A or Type B RCCB would be required. The rated breaking and making capacity is 500 A per EN/IEC 61008-1. In a domestic or light commercial distribution board, this is adequate for the prospective fault current typically seen downstream of a 63 A or 100 A main switch. The 2-pole device occupies 4 modules of 9 mm pitch (36 mm total width). Neutral is on the left. Tunnel-type terminals accept 1-35 mm² rigid or 1-25 mm² flexible conductors; tighten to 3.5 N·m.","metaTitle":"Schneider Electric A9N16202 Acti9 xID RCCB, 25 A, 300 mA, 2P","metaDescription":"Schneider Electric A9N16202 Acti9 xID residual current circuit breaker (RCCB), 25 A rated current, 300 mA sensitivity, Type AC, 2-pole, 230-240 V AC, DIN rail mount. Current produc","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"75 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"81 mm","Standards":"EN 61008-2-1 IEC 61008-2-1 EN/IEC 61008-1","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 xID","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Connection pitch":"18 mm between phases","Local signalling":"ON, OFF, fault trip","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"2","Device short name":"xID","Network frequency":"50 Hz","Poles description":"2P","Relative humidity":"95 % at 55 °C","Tightening torque":"3.5 N.m top or bottom","[In] rated current":"25 A","Electrical durability":"4000 cycles","Mechanical durability":"4000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Tunnel type terminals (top or bottom) 1...35 mm² rigid Tunnel type terminals (top or bottom) 1...25 mm² flexible","IP degree of protection":"IP20","Earth-leakage sensitivity":"300 mA","Product or component type":"Residual current circuit breaker (RCCB)","Suitability for isolation":"Yes","Contact position indicator":"Yes","Locking options description":"Padlocking device","[Ui] rated insulation voltage":"500 V AC 50 Hz","Earth-leakage protection class":"Type AC","[Ue] rated operational voltage":"230...240 V AC 50 Hz","Rated breaking and making capacity":"500 A conforming to EN/IEC 61008-1","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Ambient air temperature for operation":"-5...40 °C","[Uimp] rated impulse withstand voltage":"6 kV","Comb busbar and distribution block compatibility":"Downside: biconnect"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9N16202/acti-9-xid-residual-circuit-breaker-25-a-2p-300ma-class-ac-instantaneous/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N16202/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for A9N16202?","answer":"Submit an RFQ through this listing. Pricing and stock are confirmed at quote time — the part is sourced to order through independent distribution channels."},{"question":"What is A9N16202's listed depth?","answer":"The A9N16202 has a depth of 75 mm, a width of 36 mm (4 x 9 mm pitches), and a height of 81 mm."},{"question":"What compliance documentation does this RCCB carry?","answer":"The A9N16202 is certified to EN 61008-2-1 and IEC 61008-2-1, and meets the general requirements of EN/IEC 61008-1. It is tropicalised to class 2 per IEC 60068-1. The IP20 rating is for enclosed installation only."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N16202","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N16202 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}