{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N16203","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N16203","canonicalUrl":"https://aoctrl.com/schneider/A9N16203","factsUrl":"https://aoctrl.com/api/mcp/products/A9N16203","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 xID RCCB, A9N16203, 2P, 25 A, 100 mA sensitivity, Type AC, 230-240 V AC, DIN rail.","salesMarkdown":"The Schneider Electric A9N16203 is an Acti9 xID residual current circuit breaker (RCCB) — a 2-pole, Type AC device rated for 25 A continuous load and 100 mA earth-leakage sensitivity. The 100 mA sensitivity (Type AC) means it trips on sinusoidal AC fault currents only — suitable for general-purpose circuits where non-sinusoidal or pulsating DC leakage is not expected. The tunnel-type terminals accept up to 35 mm² rigid or 25 mm² flexible cable; stripping length is 14 mm, and tightening torque is 3.5 N·m. The 18 mm phase-to-phase pitch matches the Acti9 busbar system. Mechanical and electrical durability are both rated at 4000 cycles. The toggle provides local ON, OFF, and fault-trip indication, and a padlocking device is available for lockout/tagout.","metaTitle":"Schneider Electric A9N16203 Acti9 xID RCCB, 25 A, 100 mA, 2P","metaDescription":"Schneider Electric A9N16203 Acti9 xID RCCB, 25 A rated current, 100 mA earth-leakage sensitivity, 2-pole, Type AC, 230-240 V AC, DIN rail mount. IEC 61008. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"75 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"81 mm","Standards":"IEC 61008-2-1 EN 61008-2-1 EN/IEC 61008-1","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 xID","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Connection pitch":"18 mm between phases","Local signalling":"ON, OFF, fault trip","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"2","Device short name":"xID","Network frequency":"50 Hz","Poles description":"2P","Relative humidity":"95 % at 55 °C","Tightening torque":"3.5 N.m top or bottom","[In] rated current":"25 A","Electrical durability":"4000 cycles","Mechanical durability":"4000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Tunnel type terminals (top or bottom) 1...35 mm² rigid Tunnel type terminals (top or bottom) 1...25 mm² flexible","IP degree of protection":"IP20","Earth-leakage sensitivity":"100 mA","Product or component type":"Residual current circuit breaker (RCCB)","Suitability for isolation":"Yes","Contact position indicator":"Yes","Locking options description":"Padlocking device","[Ui] rated insulation voltage":"500 V AC 50 Hz","Earth-leakage protection class":"Type AC","[Ue] rated operational voltage":"230...240 V AC 50 Hz","Rated breaking and making capacity":"500 A conforming to EN/IEC 61008-1","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Ambient air temperature for operation":"-5...40 °C","[Uimp] rated impulse withstand voltage":"6 kV","Comb busbar and distribution block compatibility":"Downside: biconnect"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9N16203/acti-9-xid-residual-circuit-breaker-25-a-2p-100ma-class-ac-instantaneous/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N16203/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy the A9N16203 and get a price?","answer":"The A9N16203 is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."},{"question":"What are the key ratings of the A9N16203?","answer":"The A9N16203 is a 2-pole RCCB rated at 25 A, 100 mA earth-leakage sensitivity, Type AC, 230-240 V AC, with a 500 A breaking capacity per IEC 61008-1."},{"question":"What compliance standards does the A9N16203 meet?","answer":"The A9N16203 complies with IEC 61008-2-1, EN 61008-2-1, and EN/IEC 61008-1. It is rated IP20 and carries tropicalisation class 2 per IEC 60068-1."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N16203","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N16203 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}