{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N16208","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N16208","canonicalUrl":"https://aoctrl.com/schneider/A9N16208","factsUrl":"https://aoctrl.com/api/mcp/products/A9N16208","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 xID RCCB, 2P, 63 A, 30 mA, Type AC, 230-240 V AC, clip-on DIN rail.","salesMarkdown":"The breaking and making capacity is 630 A, conforming to EN/IEC 61008-1. This is a Type AC device, meaning it detects sinusoidal AC residual currents only — not pulsed DC or high-frequency components. The tunnel-type terminals accept 1-35 mm² rigid or 1-25 mm² flexible conductors; wire stripping length is 14 mm. IP20 rated — suitable for installation inside a panel or enclosure where it is protected from contact and dripping water. The toggle control provides ON, OFF, and fault-trip local signalling, and a padlocking device is available for lockout/tagout.","metaTitle":"Schneider Electric A9N16208 Acti9 xID RCCB, 63 A, 30 mA, Typ","metaDescription":"Schneider Electric A9N16208 Acti9 xID residual current circuit breaker (RCCB). 63 A rated current, 30 mA sensitivity, Type AC, 2P, 230-240 V AC. Clip-on DIN rail mount. Sourced to","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"75 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"81 mm","Standards":"EN/IEC 61008-1 IEC 61008-2-1 EN 61008-2-1","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 xID","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Connection pitch":"18 mm between phases","Local signalling":"ON, OFF, fault trip","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"2","Device short name":"xID","Network frequency":"50 Hz","Poles description":"2P","Relative humidity":"95 % at 55 °C","Tightening torque":"3.5 N.m top or bottom","[In] rated current":"63 A","Electrical durability":"4000 cycles","Mechanical durability":"4000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Tunnel type terminals (top or bottom) 1...35 mm² rigid Tunnel type terminals (top or bottom) 1...25 mm² flexible","IP degree of protection":"IP20","Earth-leakage sensitivity":"30 mA","Product or component type":"Residual current circuit breaker (RCCB)","Suitability for isolation":"Yes","Contact position indicator":"Yes","Locking options description":"Padlocking device","[Ui] rated insulation voltage":"500 V AC 50 Hz","Earth-leakage protection class":"Type AC","[Ue] rated operational voltage":"230...240 V AC 50 Hz","Rated breaking and making capacity":"630 A conforming to EN/IEC 61008-1","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Ambient air temperature for operation":"-5...40 °C","[Uimp] rated impulse withstand voltage":"6 kV","Comb busbar and distribution block compatibility":"Downside: biconnect"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9N16208/acti-9-xid-residual-circuit-breaker-63-a-2p-30ma-class-ac-instantaneous/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N16208/alternatives.json"},"ai":{"faq":[{"question":"What is A9N16208's rated current and earth-leakage sensitivity?","answer":"The A9N16208 is rated at 63 A with a 30 mA earth-leakage sensitivity, Type AC, suitable for sinusoidal AC residual currents."},{"question":"What standards does the A9N16208 comply with?","answer":"It complies with EN/IEC 61008-1 and IEC 61008-2-1, EN 61008-2-1, covering general and functional requirements for RCCBs."},{"question":"Where can I buy the A9N16208?","answer":"The A9N16208 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N16208","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N16208 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}