{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N16212","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N16212","canonicalUrl":"https://aoctrl.com/schneider/A9N16212","factsUrl":"https://aoctrl.com/api/mcp/products/A9N16212","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 xID A9N16212, 2-pole residual current circuit breaker (RCCB), 80 A, 30 mA Type AC, 230-240 V AC, DIN rail clip-on.","salesMarkdown":"## 80 A RCCB for panel builders — what the ratings mean Type AC covers the sine-wave faults most common in resistive and simple inductive loads; it does not detect pulsating DC or high-frequency residuals (those call for Type A or Type F). Mounts via clip-on to DIN rail (35 mm per EN 60715), occupying 4 x 9 mm pitches (36 mm width). The tunnel-type terminals accept 1…35 mm² rigid or 1…25 mm² flexible cable; tighten to 3.5 N·m. Designed and tested to IEC 61008-1, EN 61008-1, and IEC 61008-2-1 — the core standards for residual current operated circuit-breakers without integral overcurrent protection. Pollution degree 2 (normal industrial/domestic environment). IP20 finger-safe terminals; install inside a distribution board or enclosure rated for the ambient conditions.","metaTitle":"A9N16212 Acti9 xID RCCB 80A 30mA 2P Type AC","metaDescription":"Schneider Electric A9N16212 Acti9 xID residual current circuit breaker, 80 A rated current, 30 mA sensitivity, 2-pole Type AC, 230-240 V AC, DIN rail mount. Active production, sour","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"75 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"81 mm","Standards":"IEC 61008-2-1 EN/IEC 61008-1 EN 61008-2-1","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 xID","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Connection pitch":"18 mm between phases","Local signalling":"ON, OFF, fault trip","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"2","Device short name":"xID","Network frequency":"50 Hz","Poles description":"2P","Relative humidity":"95 % at 55 °C","Tightening torque":"3.5 N.m top or bottom","[In] rated current":"80 A","Electrical durability":"4000 cycles","Mechanical durability":"4000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Tunnel type terminals (top or bottom) 1...35 mm² rigid Tunnel type terminals (top or bottom) 1...25 mm² flexible","IP degree of protection":"IP20","Earth-leakage sensitivity":"30 mA","Product or component type":"Residual current circuit breaker (RCCB)","Suitability for isolation":"Yes","Contact position indicator":"Yes","Locking options description":"Padlocking device","[Ui] rated insulation voltage":"500 V AC 50 Hz","Earth-leakage protection class":"Type AC","[Ue] rated operational voltage":"230...240 V AC 50 Hz","Rated breaking and making capacity":"800 A conforming to EN/IEC 61008-1","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Ambient air temperature for operation":"-5...40 °C","[Uimp] rated impulse withstand voltage":"6 kV","Comb busbar and distribution block compatibility":"Downside: biconnect"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9N16212/acti-9-xid-residual-circuit-breaker-80-a-2p-30ma-class-ac-instantaneous/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N16212/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9N16212 and how do I get a price?","answer":"The A9N16212 is sourced to order against an RFQ through independent distribution. Submit a request for quote; availability and current pricing are confirmed at quote time."},{"question":"What is the closest alternative to A9N16212 in the Acti9 family?","answer":"Within the Acti9 xID range, the closest alternative is a different sensitivity or pole count variant — for example, a 30 mA Type A 2P RCCB for circuits with electronic loads that generate pulsating DC fault currents. The mechanical footprint (36 mm width, DIN rail clip-on) and terminal specifications are identical across the xID family, so swapping requires only verifying the earth-leakage protection class and rated current match the circuit design."},{"question":"What compliance documentation does Schneider provide for A9N16212?","answer":"The A9N16212 carries CE marking and is designed to meet IEC 61008-1, EN 61008-1, and IEC 61008-2-1. Standard documentation includes the declaration of conformity and the product datasheet. RoHS and REACH compliance declarations are available from Schneider Electric's documentation portal."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N16212","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N16212 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}