{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N16237","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N16237","canonicalUrl":"https://aoctrl.com/schneider/A9N16237","factsUrl":"https://aoctrl.com/api/mcp/products/A9N16237","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 xID RCCB, 2P, 40 A, 30 mA, Type A-SI, 230-240 V AC, DIN rail clip-on, white.","salesMarkdown":"## What this RCCB carries The Schneider Electric A9N16237 is an Acti9 xID residual current circuit breaker (RCCB) — 2-pole, 40 A rated current, 30 mA earth-leakage sensitivity, Type A-SI (Super Immunised). It clips onto a DIN rail, occupies 4 x 9 mm pitches (36 mm wide), and is rated for 230-240 V AC at 50 Hz. The 30 mA trip threshold covers standard personnel protection; the Type A-SI classification means it handles pulsed DC fault currents and is immunised against nuisance tripping from high-frequency leakage (switched-mode supplies, VFDs, LED drivers). Breaking capacity is 500 A per EN/IEC 61008-1. Clip-on mounting to DIN rail, neutral on the left, tunnel terminals top and bottom — accepts 1-35 mm² rigid or 1-25 mm² flexible. Wire stripping length 14 mm; tightening torque 3.5 N·m. Connection pitch is 18 mm between phases. IP20 finger-safe front, suitable for enclosed distribution boards. Local signalling shows ON, OFF, and fault trip; padlocking provision for lockout/tagout.","metaTitle":"Schneider Electric A9N16237 Acti9 xID RCCB, 40 A, 30 mA, Typ","metaDescription":"Schneider Electric A9N16237 Acti9 xID RCCB, 40 A rated current, 30 mA earth-leakage sensitivity, Type A-SI Super Immunised, 2P, 230-240 V AC, DIN rail. Active production. Sourced t","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"75 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"81 mm","Standards":"EN 61008-2-1 EN/IEC 61008-1 IEC 61008-2-1","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 xID","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Connection pitch":"18 mm between phases","Local signalling":"ON, OFF, fault trip","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"2","Device short name":"xID","Network frequency":"50 Hz","Poles description":"2P","Relative humidity":"95 % at 55 °C","Tightening torque":"3.5 N.m top or bottom","[In] rated current":"40 A","Electrical durability":"4000 cycles","Mechanical durability":"4000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Tunnel type terminals (top or bottom) 1...35 mm² rigid Tunnel type terminals (top or bottom) 1...25 mm² flexible","IP degree of protection":"IP20","Earth-leakage sensitivity":"30 mA","Product or component type":"Residual current circuit breaker (RCCB)","Suitability for isolation":"Yes","Contact position indicator":"Yes","Locking options description":"Padlocking device","[Ui] rated insulation voltage":"500 V AC 50 Hz","Earth-leakage protection class":"Type A-SI (Super Immunised)","[Ue] rated operational voltage":"230...240 V AC 50 Hz","Rated breaking and making capacity":"500 A conforming to EN/IEC 61008-1","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Ambient air temperature for operation":"-5...40 °C","[Uimp] rated impulse withstand voltage":"6 kV","Comb busbar and distribution block compatibility":"Downside: biconnect"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9N16237/acti-9-xid-residual-circuit-breaker-40-a-2p-30ma-class-si-instantaneous/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N16237/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for A9N16237?","answer":"The A9N16237 is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."},{"question":"What is A9N16237's listed depth (75 mm) on this component line?","answer":"The A9N16237 has a depth of 75 mm."},{"question":"What is A9N16237's listed range (Acti9) on this component line?","answer":"The A9N16237 belongs to the Schneider Electric Acti9 range, product name Acti9 xID."},{"question":"What compliance documentation does this brand provide for A9N16237 (RoHS, REACH, UL, IEC)?","answer":"The A9N16237 complies with EN 61008-2-1, EN/IEC 61008-1, and IEC 61008-2-1. It is tropicalised per IEC 60068-1 (class 2)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N16237","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N16237 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}