{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N16254","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N16254","canonicalUrl":"https://aoctrl.com/schneider/A9N16254","factsUrl":"https://aoctrl.com/api/mcp/products/A9N16254","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 xID RCCB, 4P, 40 A, 30 mA, Type AC, 400-415 V AC, DIN rail clip-on.","salesMarkdown":"The Schneider Electric A9N16254 is a 4-pole residual current circuit breaker (RCCB) from the Acti9 xID range, rated 40 A with 30 mA earth-leakage sensitivity. It operates on 400-415 V AC, 50 Hz, and clips onto a DIN rail for panel mounting. The 4P (four-pole) configuration switches all phases and neutral, with neutral on the left. Instantaneous trip time means no intentional delay — it clears earth faults as fast as the internal mechanism allows. This RCCB mounts in a distribution board or subpanel on a DIN rail (clip-on). The 72 mm width (8 x 9 mm pitches) fits standard modular enclosure spacing. The tunnel terminals accept up to 35 mm² rigid or 25 mm² flexible cable; strip 14 mm and tighten to 3.5 N·m. The toggle provides ON, OFF, and fault-trip indication. A padlocking device can lock the toggle in the OFF position for isolation (the device is marked suitable for isolation).","metaTitle":"Schneider Electric A9N16254 Acti9 xID RCCB, 40 A, 30 mA, 4P","metaDescription":"Schneider Electric A9N16254 Acti9 xID RCCB, 40 A rated, 30 mA sensitivity, 4P, Type AC, 400-415 V AC, DIN rail. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"75 mm","Range":"Acti9","Width":"72 mm","Colour":"White","Height":"81 mm","Standards":"EN 61008-2-1 IEC 61008-2-1 EN/IEC 61008-1","9 Mm Pitches":"8","Control type":"Toggle","Network type":"AC","Product name":"Acti9 xID","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Connection pitch":"18 mm between phases","Local signalling":"ON, OFF, fault trip","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"2","Device short name":"xID","Network frequency":"50 Hz","Poles description":"4P","Relative humidity":"95 % at 55 °C","Tightening torque":"3.5 N.m top or bottom","[In] rated current":"40 A","Electrical durability":"4000 cycles","Mechanical durability":"4000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Tunnel type terminals (top or bottom) 1...35 mm² rigid Tunnel type terminals (top or bottom) 1...25 mm² flexible","IP degree of protection":"IP20","Earth-leakage sensitivity":"30 mA","Product or component type":"Residual current circuit breaker (RCCB)","Suitability for isolation":"Yes","Contact position indicator":"Yes","Locking options description":"Padlocking device","[Ui] rated insulation voltage":"500 V AC 50 Hz","Earth-leakage protection class":"Type AC","[Ue] rated operational voltage":"400...415 V AC 50 Hz","Rated breaking and making capacity":"500 A conforming to EN/IEC 61008-1","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Ambient air temperature for operation":"-5...40 °C","[Uimp] rated impulse withstand voltage":"6 kV","Comb busbar and distribution block compatibility":"Downside: biconnect"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9N16254/acti-9-xid-residual-circuit-breaker-40-a-4p-30ma-class-ac-instantaneous/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N16254/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings of A9N16254?","answer":"The A9N16254 is a 4-pole RCCB rated 40 A, 30 mA sensitivity, Type AC, 400-415 V AC, 50 Hz, with a breaking capacity of 500 A conforming to EN/IEC 61008-1."},{"question":"Where can I buy A9N16254?","answer":"The A9N16254 is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."},{"question":"What compliance documentation does Schneider Electric provide for A9N16254?","answer":"The A9N16254 complies with EN 61008-2-1, IEC 61008-2-1, and EN/IEC 61008-1 standards. It is tropicalised to class 2 per IEC 60068-1, and carries IP20 protection. Documentation such as the datasheet and declaration of conformity is available from the manufacturer."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N16254","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N16254 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}