{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N16258","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N16258","canonicalUrl":"https://aoctrl.com/schneider/A9N16258","factsUrl":"https://aoctrl.com/api/mcp/products/A9N16258","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 xID, A9N16258, 4P residual current circuit breaker, 63 A, 30 mA, Type AC, 400-415 V AC, clip-on DIN rail.","salesMarkdown":"The 63 A rated current means it handles the full incoming supply for a typical sub-main or large final circuit, not just a branch load. Clip-on DIN rail mount, 72 mm wide — that's 8 modules of 9 mm pitch. Neutral on the left, 18 mm phase-to-phase terminal spacing. Tunnel terminals accept up to 35 mm² rigid or 25 mm² flexible; strip 14 mm and torque to 3.5 N.m. IP20 front, so it lives inside an enclosed panel, not on the wet side of the gland plate. The padlocking device and contact-position indicator make lockout/tagout straightforward for the field-service tech who has to swap it fast. The Acti9 xID family is a standard line, so this order code is a straightforward BOM line item.","metaTitle":"A9N16258 Acti9 xID RCCB, 63 A, 30 mA, 4P, Type AC","metaDescription":"Schneider Electric A9N16258 Acti9 xID 4-pole RCCB. Rated 63 A, 30 mA earth-leakage sensitivity, Type AC, 400-415 V AC. Current production. Quoted on request.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"75 mm","Range":"Acti9","Width":"72 mm","Colour":"White","Height":"81 mm","Standards":"IEC 61008-2-1 EN 61008-2-1 EN/IEC 61008-1","9 Mm Pitches":"8","Control type":"Toggle","Network type":"AC","Product name":"Acti9 xID","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Connection pitch":"18 mm between phases","Local signalling":"ON, OFF, fault trip","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"2","Device short name":"xID","Network frequency":"50 Hz","Poles description":"4P","Relative humidity":"95 % at 55 °C","Tightening torque":"3.5 N.m top or bottom","[In] rated current":"63 A","Electrical durability":"4000 cycles","Mechanical durability":"4000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Tunnel type terminals (top or bottom) 1...35 mm² rigid Tunnel type terminals (top or bottom) 1...25 mm² flexible","IP degree of protection":"IP20","Earth-leakage sensitivity":"30 mA","Product or component type":"Residual current circuit breaker (RCCB)","Suitability for isolation":"Yes","Contact position indicator":"Yes","Locking options description":"Padlocking device","[Ui] rated insulation voltage":"500 V AC 50 Hz","Earth-leakage protection class":"Type AC","[Ue] rated operational voltage":"400...415 V AC 50 Hz","Rated breaking and making capacity":"630 A conforming to EN/IEC 61008-1","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Ambient air temperature for operation":"-5...40 °C","[Uimp] rated impulse withstand voltage":"6 kV","Comb busbar and distribution block compatibility":"Downside: biconnect"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/A9N16258/acti-9-xid-residual-circuit-breaker-63-a-4p-30ma-class-ac-instantaneous/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N16258/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for the A9N16258?","answer":"63 A rated current, 30 mA earth-leakage sensitivity, Type AC, 4 poles, rated operational voltage 400-415 V AC at 50 Hz, breaking capacity 630 A per IEC 61008-1."},{"question":"What compliance documentation covers this RCCB?","answer":"The A9N16258 is certified to IEC 61008-1, EN 61008-1, and EN/IEC 61008-2-1. It carries IP20 protection and meets tropicalisation class 2 per IEC 60068-1."},{"question":"Where can I buy the A9N16258?","answer":"Sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N16258","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N16258 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}