{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N18382","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N18382","canonicalUrl":"https://aoctrl.com/schneider/A9N18382","factsUrl":"https://aoctrl.com/api/mcp/products/A9N18382","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 C120N, A9N18382, miniature circuit breaker, D curve, 63 A, 2 poles, 10 kA Icn at 400 V AC.","salesMarkdown":"The Schneider Electric A9N18382 is a 2-pole Acti9 C120N miniature circuit breaker with a D tripping curve, rated 63 A at 30 °C. Rated at 10 kA Icn at 400 V AC per EN/IEC 60898-1, and 6 kA Icu at 440 V AC per EN/IEC 60947-2. The D curve (10–14 x In magnetic trip) is sized for transformer inrush and motor-start loads — not general lighting or resistive circuits. The thermal-magnetic trip unit handles overloads on the bimetal side and short-circuits on the solenoid side. Listed as current production. This is a standard-catalogue Acti9 C120N — no phase-out notice, no last-time-buy window.","metaTitle":"Schneider Electric A9N18382 Acti9 C120N MCB, D Curve, 63 A,","metaDescription":"Schneider Electric A9N18382 Acti9 C120N miniature circuit breaker, D curve, 63 A, 2 poles, 10 kA breaking capacity at 400 V AC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"White","Depth":"73 mm","Width":"54 mm","Height":"81 mm","Voltage":"380...415 V AC 50/60 Hz 220...240 V AC 50/60 Hz 440 V AC 50/60 Hz 230...400 V AC 50/60 Hz","IP Rating":"IP20","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to IEC 60947-2","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Breaking Capacity":"10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2","Insulation Voltage Ui":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Electrical Life Cycles":"10000 cycles conforming to IEC 60947-2","Mechanical Life Cycles":"20000 cycles","Main Product Or Component Type":"Miniature circuit-breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e4241f7bbb5bea80716d588a08abbb6b.pdf","sourceUrl":"https://www.se.com/be/en/product/A9N18382/miniature-circuit-breaker-mcb-acti9-c120n-2p-63a-d-curve-10000a-iec-en-608981-10ka-iec-en-609472/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N18382/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N18382","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N18382 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}