{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N18390","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N18390","canonicalUrl":"https://aoctrl.com/schneider/A9N18390","factsUrl":"https://aoctrl.com/api/mcp/products/A9N18390","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 C120N miniature circuit breaker, A9N18390, 4-pole, D curve, 63 A rated current, 10 kA breaking capacity at 400 V AC.","salesMarkdown":"The A9N18390 is a 4-pole Acti9 C120N miniature circuit breaker rated 63 A at 30 °C with a D tripping curve (10–14 × In magnetic trip). Breaking capacity is 10 kA Icn at 400 V AC per EN/IEC 60898-1, and 6 kA Icu at 440 V AC per EN/IEC 60947-2. For DC circuits it's rated 10 kA Icu at ≤500 V DC, so it works on 480 V DC bus applications too. Dual-rated to EN/IEC 60898-1 and EN/IEC 60947-2, which means it qualifies both as a domestic MCB and as an industrial circuit breaker for isolation duty (suitability for isolation confirmed per IEC 60947-2). At 108 mm wide (12 × 9 mm pitches) for 4 poles, it occupies the expected 4-module width in a distribution board. Tunnel terminals accept 1–50 mm² rigid or 1.5–35 mm² flexible, with a 3.5 N·m tightening torque and 15 mm strip length — standard for panel wiring with no surprises. IP20 finger protection on the front, so it's safe for open-panel mounting but not for washdown areas.","metaTitle":"Schneider Electric A9N18390 Acti9 C120N MCB, D Curve, 63 A,","metaDescription":"Schneider Electric A9N18390 Acti9 C120N miniature circuit breaker. 63 A, D curve, 4 poles, 10 kA breaking capacity at 400 V. Current lifecycle stage. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"White","Depth":"73 mm","Width":"108 mm","Height":"81 mm","Voltage":"380...415 V AC 50/60 Hz 220...240 V AC 50/60 Hz 440 V AC 50/60 Hz 230...400 V AC 50/60 Hz","IP Rating":"IP20","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to IEC 60947-2","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Breaking Capacity":"10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at <= 500 V DC conforming to EN/IEC 60947-2","Insulation Voltage Ui":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-40...85 °C","Electrical Life Cycles":"10000 cycles conforming to IEC 60947-2","Mechanical Life Cycles":"20000 cycles","Main Product Or Component Type":"Miniature circuit-breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f444046efdd1e34a1a1743c923236bbe.pdf","sourceUrl":"https://www.se.com/ae/en/product/A9N18390/c120n-circuit-breaker-4p-63a-d-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N18390/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N18390","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N18390 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}