{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N18413","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N18413","canonicalUrl":"https://aoctrl.com/schneider/A9N18413","factsUrl":"https://aoctrl.com/api/mcp/products/A9N18413","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 C120H miniature circuit breaker, A9N18413, 80 A rated, B-curve, 2-pole, 15 kA breaking capacity at 400 V AC, thermal-magnetic trip, clip-on 35 mm DIN rail.","salesMarkdown":"The Schneider Electric A9N18413 is an Acti9 C120H miniature circuit breaker (MCB) rated 80 A at 30 °C with a B-curve trip characteristic (magnetic tripping between 3 and 5 x In). The headline breaking capacity is 15 kA Icn at 400 V AC 50/60 Hz per EN/IEC 60898-1, with an Icu of 10 kA at 440 V AC and 30 kA at 220–240 V AC per EN/IEC 60947-2. This dual-standard rating means the breaker is certified for both residential (60898-1) and industrial (60947-2) fault-clearing requirements, giving the specifying engineer flexibility in panel design without swapping hardware. Mounts via clip-on to 35 mm DIN rail — standard for panel and enclosure integration. The 54 mm width (9 mm pitch × 6) occupies six modular spaces, which is typical for a 2-pole 80 A MCB in the Acti9 range. Tunnel-type terminals accept 1–50 mm² rigid or 1.5–35 mm² flexible conductors; wire strip length is 15 mm, tightening torque 3.5 N·m. IP20 finger-safe protection is suitable for enclosed panels. Dual-certified to EN/IEC 60898-1 (MCB standard for household and similar installations) and EN/IEC 60947-2 (low-voltage switchgear and controlgear standard for industrial application). This dual certification is the key differentiator: the same breaker satisfies both a domestic distribution board spec and an industrial panel SCCR study. Electrical durability is 5,000 cycles (IEC 60947-2), mechanical durability 20,000 cycles. Earth-leakage protection requires a separate block (not integrated).","metaTitle":"Schneider Electric A9N18413 Acti9 C120H MCB, 80 A B-Curve 2P","metaDescription":"Schneider Electric A9N18413 Acti9 C120H miniature circuit breaker, 80 A rated, B-curve, 2-pole, 15 kA breaking capacity at 400 V AC. Dual-certified EN/IEC 60898-1 & 60947-2. Curren","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"73 mm","Range":"Acti9","Width":"54 mm","title":"A9N18413","Colour":"White","Height":"81 mm","Standards":"EN/IEC 60898-1 EN/IEC 60947-2","Curve code":"B","description":"Miniature circuit breaker (MCB), Acti9 C120H, 2P, 80A, B curve, 15000A (IEC/EN 60898-1), 15kA (IEC/EN 60947-2)","9 Mm Pitches":"6","Control type":"Toggle","Network type":"AC","Product name":"Acti9 C120","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60947-2","Local signalling":"ON/OFF indication","Mounting support":"35 mm symmetrical DIN rail","Neutral position":"Left","Pollution degree":"3 conforming to IEC 60947-2","Breaking capacity":"15000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2","Device short name":"C120H","Network frequency":"50/60 Hz","Poles description":"2P","Relative humidity":"95 % at 55 °C","Tightening torque":"3.5 N.m","Device application":"Distribution","Operating altitude":"2000 m","[In] rated current":"80 A at 30 °C","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Electrical durability":"5000 cycles conforming to IEC 60947-2","Mechanical durability":"20000 cycles","Wire stripping length":"15 mm","Connections - terminals":"Tunnel type terminals1...50 mm² rigid Tunnel type terminals1.5...35 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"3...5 x In","Earth-leakage protection":"Separate block","Number of protected poles":"2","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","Locking options description":"Handle sealable with cable diameter 0.7mm in OFF or ON position","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","[Ue] rated operational voltage":"380...415 V AC 50/60 Hz 220...240 V AC 50/60 Hz 440 V AC 50/60 Hz 230...400 V AC 50/60 Hz","Ambient air temperature for storage":"-40...70 °C","Ambient air temperature for operation":"-30...60 °C","[Ics] rated service breaking capacity":"7500 A 50 % conforming to EN/IEC 60898-1 - 400 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 15 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - <= 250 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2","Comb busbar and distribution block compatibility":"YES"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/93353ff06f8292dc818b6ae7cd9fa967.pdf","sourceUrl":"https://www.se.com/ie/en/product/A9N18413/miniature-circuit-breaker-mcb-acti9-c120h-2p-80a-b-curve-15000a-iec-en-608981-15ka-iec-en-609472/"},"ai":{"faq":[{"question":"What is the breaking capacity of A9N18413?","answer":"The A9N18413 has a breaking capacity of 15 kA Icn at 400 V AC per EN/IEC 60898-1, and an Icu of 10 kA at 440 V AC, 15 kA at 380–415 V AC, and 30 kA at 220–240 V AC per EN/IEC 60947-2."},{"question":"What standards does A9N18413 comply with?","answer":"The A9N18413 is dual-certified to EN/IEC 60898-1 and EN/IEC 60947-2, covering both household and industrial switchgear standards."},{"question":"Where can I buy A9N18413?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time."},{"question":"What is the rated current of A9N18413?","answer":"The rated current (In) is 80 A at 30 °C, with a B-curve trip characteristic (magnetic trip between 3 and 5 x In)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N18413","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N18413 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}