{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N18413","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N18413","canonicalUrl":"https://aoctrl.com/schneider/A9N18413","factsUrl":"https://aoctrl.com/api/mcp/products/A9N18413","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 C120H miniature circuit breaker, A9N18413, 80 A rated, B-curve, 2-pole, 15 kA breaking capacity at 400 V AC, thermal-magnetic trip, clip-on 35 mm DIN rail.","salesMarkdown":"The Schneider Electric A9N18413 is an Acti9 C120H miniature circuit breaker (MCB) rated 80 A at 30 °C with a B-curve trip characteristic (magnetic tripping between 3 and 5 x In). The headline breaking capacity is 15 kA Icn at 400 V AC 50/60 Hz per EN/IEC 60898-1, with an Icu of 10 kA at 440 V AC and 30 kA at 220–240 V AC per EN/IEC 60947-2. This dual-standard rating means the breaker is certified for both residential (60898-1) and industrial (60947-2) fault-clearing requirements, giving the specifying engineer flexibility in panel design without swapping hardware. Mounts via clip-on to 35 mm DIN rail — standard for panel and enclosure integration. The 54 mm width (9 mm pitch × 6) occupies six modular spaces, which is typical for a 2-pole 80 A MCB in the Acti9 range. Tunnel-type terminals accept 1–50 mm² rigid or 1.5–35 mm² flexible conductors; wire strip length is 15 mm, tightening torque 3.5 N·m. IP20 finger-safe protection is suitable for enclosed panels. Dual-certified to EN/IEC 60898-1 (MCB standard for household and similar installations) and EN/IEC 60947-2 (low-voltage switchgear and controlgear standard for industrial application). This dual certification is the key differentiator: the same breaker satisfies both a domestic distribution board spec and an industrial panel SCCR study. Electrical durability is 5,000 cycles (IEC 60947-2), mechanical durability 20,000 cycles. Earth-leakage protection requires a separate block (not integrated).","metaTitle":"Schneider Electric A9N18413 Acti9 C120H MCB, 80 A B-Curve 2P","metaDescription":"Schneider Electric A9N18413 Acti9 C120H miniature circuit breaker, 80 A rated, B-curve, 2-pole, 15 kA breaking capacity at 400 V AC. Dual-certified EN/IEC 60898-1 & 60947-2. Curren","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"White","Depth":"73 mm","Width":"54 mm","Height":"81 mm","Voltage":"380...415 V AC 50/60 Hz 220...240 V AC 50/60 Hz 440 V AC 50/60 Hz 230...400 V AC 50/60 Hz","IP Rating":"IP20","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to IEC 60947-2","Temp Storage Max":"70 °C","Temp Storage Min":"-40 °C","Insulation Voltage Ui":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Temp Operating Max":"60 °C","Temp Operating Min":"-30 °C","Temperature Storage":"-40...70 °C","Electrical Life Cycles":"5000 cycles conforming to IEC 60947-2","Mechanical Life Cycles":"20000 cycles","Main Product Or Component Type":"Miniature circuit-breaker","Ambient Air Temperature Operation":"-30...60 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/93353ff06f8292dc818b6ae7cd9fa967.pdf","sourceUrl":"https://www.se.com/ie/en/product/A9N18413/miniature-circuit-breaker-mcb-acti9-c120h-2p-80a-b-curve-15000a-iec-en-608981-15ka-iec-en-609472/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N18413/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N18413","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N18413 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}