{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N18500","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N18500","canonicalUrl":"https://aoctrl.com/schneider/A9N18500","factsUrl":"https://aoctrl.com/api/mcp/products/A9N18500","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 C120H, A9N18500, miniature circuit breaker, 2P, 63 A, D curve, 15 kA Icn at 400 V AC.","salesMarkdown":"The A9N18500 is a 2-pole miniature circuit breaker from the Acti9 C120H range, rated 63 A at 30 °C with a D tripping curve (magnetic trip 10–14 × In). The D curve means it tolerates the high inrush of motor and transformer loads without nuisance tripping — the magnetic trip won't fire until the fault hits 10 to 14 times the 63 A rating, so a 3-phase motor starting at 6× FLC coasts right through. Breaking capacity is 15 kA Icn at 400 V AC per EN/IEC 60898-1, and 10 kA Icu at 440 V AC per EN/IEC 60947-2 — that's enough for most industrial distribution panels downstream of a 200 kVA transformer. ## Dual-standard compliance and isolation This breaker carries both EN/IEC 60898-1 (MCB standard) and EN/IEC 60947-2 (industrial circuit-breaker standard) approvals. That dual rating means it's accepted for residential and commercial boards (60898-1) and for industrial panels where the higher Icu and isolation requirements of 60947-2 apply.","metaTitle":"Schneider Electric A9N18500 Acti9 C120H MCB, 63 A D Curve, 2","metaDescription":"Schneider Electric A9N18500 Acti9 C120H miniature circuit breaker, 63 A, D curve, 2-pole, 15 kA breaking capacity at 400 V AC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Color":"White","Depth":"73 mm","Width":"54 mm","Height":"81 mm","Voltage":"380...415 V AC 50/60 Hz 220...240 V AC 50/60 Hz 440 V AC 50/60 Hz 230...400 V AC 50/60 Hz","IP Rating":"IP20","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to IEC 60947-2","Temp Storage Max":"70 °C","Temp Storage Min":"-40 °C","Breaking Capacity":"15000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2","Insulation Voltage Ui":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Temp Operating Max":"60 °C","Temp Operating Min":"-30 °C","Temperature Storage":"-40...70 °C","Electrical Life Cycles":"10000 cycles conforming to IEC 60947-2","Mechanical Life Cycles":"20000 cycles","Main Product Or Component Type":"Miniature circuit-breaker","Ambient Air Temperature Operation":"-30...60 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7fe81bc134560f7e34fbd0a3e2071e92.pdf","sourceUrl":"https://www.se.com/nz/en/product/A9N18500/miniature-circuit-breaker-mcb-acti9-c120h-2p-63a-d-curve-15000a-iec-en-608981-15ka-iec-en-609472/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N18500/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N18500","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N18500 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}