{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N18563","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N18563","canonicalUrl":"https://aoctrl.com/schneider/A9N18563","factsUrl":"https://aoctrl.com/api/mcp/products/A9N18563","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 Vigi C120, add-on residual current device, 2P, 125A, AC type, instantaneous, 30mA, 230-240VAC, clip-on DIN rail mount.","salesMarkdown":"Rated at 125 A (In) with a 30 mA earth-leakage sensitivity, this RCD sits on the high-current end of the Acti9 Vigi C120 range. The 30 mA trip threshold is the standard for personnel protection against direct-contact faults — it catches leakage currents that would be dangerous through the chest path, while avoiding nuisance tripping from normal cable capacitance on a clean installation. ## Standards and installation conditions Designed and certified to EN 61009 and IEC/EN 61009-2-1, with a rated insulation voltage of 500 V AC and impulse withstand of 6 kV per IEC 60947-2. IP20 finger-safe terminals only — it lives inside an enclosure, not exposed to washdown. Schneider Electric lists the A9N18563 as an active product. No end-of-life notice or successor part has been published as of the latest records.","metaTitle":"Schneider Electric A9N18563 Acti9 Vigi C120, 2P, 125A, 30mA","metaDescription":"Schneider Electric A9N18563 Acti9 Vigi C120 add-on RCD, 2P, 125A, 30mA AC type, instantaneous. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"73 mm","Range":"Acti9","Width":"117 mm","title":"A9N18563","Colour":"White","Height":"95 mm","Standards":"EN 61009 IEC/EN 61009-2-1","description":"Add-on residual current device, Acti9 Vigi C120, 2P, 125A, AC type, instantaneous, 30mA, 230...240VAC","9 Mm Pitches":"7","Network type":"AC","Product name":"Acti9 Vigi C120","Mounting mode":"Clip-on","lifecycle_stage":"current","Mounting support":"35 mm symmetrical DIN rail","Pollution degree":"3 conforming to IEC 60947-2","Device short name":"Vigi C120","Network frequency":"50/60 Hz","Poles description":"2P","Tightening torque":"3.5 N.m","[In] rated current":"125 A","Mechanical durability":"20000 cycles","Wire stripping length":"15 mm","Connections - terminals":"Tunnel type terminals 1...35 mm² flexible Tunnel type terminals 1...50 mm² rigid","IP degree of protection":"IP20","Device location in system":"Outgoer Group incomer","Earth-leakage sensitivity":"30 mA","Product or component type":"Add-on residual current device","Electrical connection to mcb":"By screws","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to IEC 60947-1","Earth-leakage protection class":"Type AC","[Ue] rated operational voltage":"230...240 V AC 50/60 Hz","Ambient air temperature for storage":"-40...60 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-5...60 °C","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/67d09b4ddd5fd1f0247effd2b1baf96e.pdf","sourceUrl":"https://www.se.com/ie/en/product/A9N18563/addon-residual-current-device-acti9-vigi-c120-2p-125a-ac-type-instantaneous-30ma-230-240vac/"},"ai":{"faq":[{"question":"How do I get current pricing and availability for A9N18563?","answer":"The A9N18563 is sourced and quoted to order against an RFQ through independent distribution. Submit a request for current pricing and confirmed availability at quote time."},{"question":"What is A9N18563's listed depth (73 mm) on this component line?","answer":"The A9N18563 has a depth of 73 mm, a width of 117 mm, and a height of 95 mm, occupying 7 pitches of 9 mm on the DIN rail."},{"question":"What compliance documentation does this brand provide for A9N18563?","answer":"The A9N18563 is certified to EN 61009 and IEC/EN 61009-2-1, with a rated insulation voltage of 500 V AC and impulse withstand of 6 kV per IEC 60947-2. It carries pollution degree 3 rating per IEC 60947-2."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N18563","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N18563 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}