{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N19632","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N19632","canonicalUrl":"https://aoctrl.com/schneider/A9N19632","factsUrl":"https://aoctrl.com/api/mcp/products/A9N19632","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 DPN Vigi, Type A-SI (Super Immunised) RCBO, 1P+N, 10 A, C-curve, 30 mA earth leakage, 6 kA, DIN rail.","salesMarkdown":"It carries a 10 A rated current (C-curve thermal-magnetic trip) and 30 mA earth-leakage sensitivity, with a 6 kA breaking capacity at 230 V AC per EN 61009. The Type A-SI (Super Immunised) designation means the residual-current detection is immune to nuisance tripping from high-frequency harmonics or pulsed DC waveforms — common on variable-speed drives, LED lighting, and switched-mode power supplies. That makes this unit a fit for mixed-load final circuits where standard Type A or AC RCDs would false-trip. The 10 A rating at 30 °C sets the continuous load limit for the protected circuit — sized for lighting, small appliance, or general-purpose socket-outlet groups. The 30 mA sensitivity meets the touch-protection threshold for socket circuits in most residential and commercial codes. Operating altitude to 2000 m.","metaTitle":"Schneider Electric A9N19632 DPN Vigi 10A Type A-SI RCBO, 30","metaDescription":"Schneider Electric A9N19632 Acti9 DPN Vigi RCBO, 10 A rated, 30 mA sensitivity, Type A-SI (Super Immunised), 6 kA breaking capacity, DIN rail mount. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Type":"Type A-SI (Super Immunised)","Range":"Acti9","Colour":"White","Standards":"EN/IEC 61009-1 EN/IEC 61009-2-1","Curve code":"C","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"DPN Vigi","Embedding depth":"72 mm","Tropicalisation":"2 conforming to EN 61009","lifecycle_stage":"current","Limitation class":"3 conforming to EN 61009","Local signalling":"ON/OFF indication","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3 conforming to EN 61009","Breaking capacity":"6000 A Icn at 230 V AC conforming to EN 61009","Device short name":"DPN N Vigi","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Operating altitude":"2000 m","[In] rated current":"10 A at 30 °C","Overvoltage category":"III","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles conforming to IEC 61009","Mechanical durability":"20000 cycles","Connections - terminals":"Tunnel type terminals1 cable(s) 10 mm² flexible Tunnel type terminals1 cable(s) 16 mm² rigid","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Number of protected poles":"1","Product or component type":"Earth leakage circuit breaker","Contact position indicator":"Yes","Circuit breaker application":"Distribution","[Ui] rated insulation voltage":"400 V AC conforming to EN 61009","[Ue] rated operational voltage":"230 V AC","Ambient air temperature for storage":"-40...60 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"6000 A at 230 V AC 50/60 Hz conforming to EN 61009","[Uimp] rated impulse withstand voltage":"4 kV conforming to EN 61009"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6e0b45fd8c229d84a08966bbaeec7f97.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9N19632/residual-current-breaker-with-overcurrent-protection-rcbo-acti9-dpn-n-vigi-1p+n-10a-30ma-asi-type-6000a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N19632/alternatives.json"},"ai":{"faq":[{"question":"What is the Type A-SI (Super Immunised) rating on this RCBO?","answer":"The Type A-SI (Super Immunised) designation means the residual-current circuit is designed to resist nuisance tripping from high-frequency harmonics and pulsed DC waveforms — typical on VFD, LED, and SMPS loads."},{"question":"What standards does the A9N19632 comply with?","answer":"It complies with EN/IEC 61009-1 and EN/IEC 61009-2-1, covering combined overcurrent and residual-current circuit breakers for household and similar installations."},{"question":"Where can I buy the A9N19632?","answer":"The A9N19632 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N19632","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N19632 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}