{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N19634","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N19634","canonicalUrl":"https://aoctrl.com/schneider/A9N19634","factsUrl":"https://aoctrl.com/api/mcp/products/A9N19634","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 DPN Vigi RCBO, Type A-SI (Super Immunised), 1P+N, 16 A, 30 mA, C curve, 6 kA Icn.","salesMarkdown":"The 16 A rated current (In) at 30 °C is the continuous load it carries in a 30 °C ambient; the C-curve magnetic trip operates at 5–10 × In (80–160 A), so it handles motor inrush and transformer energisation without nuisance tripping on circuits that don't need a B or D curve. The 30 mA sensitivity catches line-to-ground faults that could be lethal through a person, and the Type A-SI (Super Immunised) designation means the electronic trip is hardened against pulsed DC and high-frequency leakage — common on variable-speed drives, LED drivers, and UPS-fed circuits where a standard Type A or AC RCD would nuisance-trip. Mounts on a 35 mm DIN rail, 36 mm wide (4 × 9 mm pitches), 77.5 mm deep, 81 mm tall. Tunnel terminals top and bottom accept 1–16 mm² rigid or 1–10 mm² flexible with ferrule; strip length 15 mm, tighten to 2 N·m. Neutral is on the left. IP20 on the body, IP40 inside a modular enclosure. Pollution degree 3, overvoltage category IV — rated for the harsh end of a distribution board.","metaTitle":"Schneider Electric A9N19634 Acti9 DPN Vigi RCBO, Type A-SI,","metaDescription":"Schneider Electric A9N19634 Acti9 DPN Vigi RCBO. 16 A rated, 30 mA earth leakage, Type A-SI super immunised, C curve, 6 kA breaking capacity. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Type":"Type A-SI (Super Immunised)","Depth":"77.5 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"81 mm","Standards":"EN/IEC 61009-1 EN/IEC 61009-2-1","Curve code":"C","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"DPN Vigi","Embedding depth":"44 mm","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN 61009","Local signalling":"ON/OFF indication","Mounting support":"35 mm DIN rail","Neutral position":"Left","Pollution degree":"3 conforming to EN 61009","Breaking capacity":"6000 A Icn at 230 V AC conforming to EN 61009","Device short name":"DPN N Vigi","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Operating altitude":"2000 m","[In] rated current":"16 A at 30 °C","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Electrical durability":"20000 cycles conforming to IEC 61009","Mechanical durability":"20000 cycles","Wire stripping length":"15 mm for top or bottom connection","Connections - terminals":"Tunnel type terminals (top or bottom) 1...10 mm² flexible with ferrule Tunnel type terminals (top or bottom) 1...16 mm² rigid","IP degree of protection":"IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Number of protected poles":"1","Product or component type":"Earth leakage circuit breaker","Contact position indicator":"Yes","Circuit breaker application":"Distribution","[Ui] rated insulation voltage":"400 V AC conforming to EN 61009","[Ue] rated operational voltage":"230 V AC","Ambient air temperature for storage":"-30...70 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"6000 A at 230 V AC 50/60 Hz conforming to EN 61009","[Uimp] rated impulse withstand voltage":"4 kV conforming to EN 61009"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/8471ee39f31bc05ef50de01ba7bd5f53.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9N19634/residual-current-breaker-with-overcurrent-protection-rcbo-acti9-dpn-n-vigi-1p+n-16a-30ma-asi-type-6000a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N19634/alternatives.json"},"ai":{"faq":[{"question":"What is the closest alternative to the A9N19634 in the Acti9 range?","answer":"The A9N19634 is a DPN Vigi RCBO with Type A-SI super-immunised electronics. The standard Type A variant (e.g. A9N18558) shares the same 16 A, 30 mA, C-curve ratings but lacks the super-immunised filtering — choose the A-SI if the downstream load includes drives, LED drivers, or UPS supplies where pulsed DC leakage is present."},{"question":"Where can I buy the A9N19634?","answer":"Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."},{"question":"What compliance documentation does Schneider provide for the A9N19634?","answer":"The part is certified to EN/IEC 61009-1 and EN/IEC 61009-2-1, limitation class 3, tropicalisation class 2 per IEC 60068-1. Pollution degree 3, overvoltage category IV. RoHS and REACH declarations are standard for the Acti9 range."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N19634","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N19634 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}