{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N19635","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N19635","canonicalUrl":"https://aoctrl.com/schneider/A9N19635","factsUrl":"https://aoctrl.com/api/mcp/products/A9N19635","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 DPN Vigi RCBO, Type A-SI (Super Immunised), 1P+N, 20 A, 30 mA, Curve C, 6 kA Icn at 230 V AC, DIN rail mount.","salesMarkdown":"The Type A-SI (Super Immunised) designation means the residual-current detection is filtered to ignore high-frequency leakage currents that would nuisance-trip a standard Type A device. This matters on circuits feeding variable-speed drives, UPS systems, or switch-mode power supplies where normal operating leakage contains harmonics and high-frequency components. ## Integration notes Terminals accept up to 10 mm² flexible or 16 mm² rigid cable — tunnel-type, so strip length and ferrule selection follow standard practice for RCBOs. The toggle control provides local ON/OFF indication and a contact position indicator for visual confirmation of state. Rated for 20000 electrical cycles and 20000 mechanical cycles per IEC 61009, which covers the duty cycle of a distribution outgoer in a typical panel. Environmental limits: storage from -40 to 60 °C, operating altitude up to 2000 m, and 95 % relative humidity at 55 °C. Tropicalisation class 2 per EN 61009 and pollution degree 3 mean it is rated for environments with conductive pollution or occasional condensation — typical of industrial enclosures not fully climate-controlled.","metaTitle":"Schneider Electric A9N19635 DPN Vigi RCBO, 20 A, 30 mA, Type","metaDescription":"Schneider Electric A9N19635 Acti9 DPN Vigi RCBO. 20 A rated current, 30 mA earth-leakage, Type A-SI (Super Immunised), Curve C, 6 kA breaking capacity. Sourced to order against RFQ","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Type":"Type A-SI (Super Immunised)","Range":"Acti9","Colour":"White","Standards":"EN/IEC 61009-1 EN/IEC 61009-2-1","Curve code":"C","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"DPN Vigi","Embedding depth":"72 mm","Tropicalisation":"2 conforming to EN 61009","lifecycle_stage":"current","Limitation class":"3 conforming to EN 61009","Local signalling":"ON/OFF indication","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3 conforming to EN 61009","Breaking capacity":"6000 A Icn at 230 V AC conforming to EN 61009","Device short name":"DPN N Vigi","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Operating altitude":"2000 m","[In] rated current":"20 A at 30 °C","Overvoltage category":"III","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles conforming to IEC 61009","Mechanical durability":"20000 cycles","Connections - terminals":"Tunnel type terminals1 cable(s) 10 mm² flexible Tunnel type terminals1 cable(s) 16 mm² rigid","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"30 mA","Number of protected poles":"1","Product or component type":"Earth leakage circuit breaker","Contact position indicator":"Yes","Circuit breaker application":"Distribution","[Ui] rated insulation voltage":"400 V AC conforming to EN 61009","[Ue] rated operational voltage":"230 V AC","Ambient air temperature for storage":"-40...60 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"6000 A at 230 V AC 50/60 Hz conforming to EN 61009","[Uimp] rated impulse withstand voltage":"4 kV conforming to EN 61009"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/66052a248cb25a5a265b6e444e0e3df4.pdf","sourceUrl":"https://www.se.com/in/en/product/A9N19635/acti-9-earth-leakage-circuit-breaker-dpn-vigi-1p-+-n-20a-30ma/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N19635/alternatives.json"},"ai":{"faq":[{"question":"What does Type A-SI (Super Immunised) mean on this RCBO?","answer":"Type A-SI (Super Immunised) means the residual-current detector is filtered to ignore high-frequency leakage currents that would nuisance-trip a standard Type A device. It is specified for circuits with VFDs, UPS systems, or SMPS where normal operating leakage contains harmonics."},{"question":"What is the breaking capacity of the A9N19635?","answer":"The breaking capacity is 6000 A Icn at 230 V AC per EN 61009, suitable for residential and light commercial distribution boards."},{"question":"What compliance standards does the A9N19635 meet?","answer":"The A9N19635 is certified to EN/IEC 61009-1 and EN/IEC 61009-2-1. It carries overvoltage category III, pollution degree 3, and tropicalisation class 2 per those standards."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N19635","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N19635 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}