{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N19643","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N19643","canonicalUrl":"https://aoctrl.com/schneider/A9N19643","factsUrl":"https://aoctrl.com/api/mcp/products/A9N19643","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 DPN Vigi, Type A-SI (Super Immunised) RCBO, 1P+N, 13 A, C-curve, 30 mA earth leakage, 6 kA breaking capacity.","salesMarkdown":"Rated 13 A at 30 °C with a C-curve magnetic trip (5–10 × In) and 300 mA earth-leakage sensitivity, it breaks up to 6000 A Icn at 230 V AC per EN/IEC 61009. The Type A-SI (Super Immunised) designation means it resists nuisance tripping from high-frequency leakage currents common on modern electronic loads — switched-mode power supplies, VFDs, LED drivers — that would trip a standard Type A device. Snaps onto standard DIN rail (mounting support per). Occupies 4 × 9 mm pitches — a single 36 mm width — so it fits a compact outgoer position in a residential or light-commercial distribution board. Embedding depth is 72 mm, leaving clearance behind the gland plate in a standard 100 mm enclosure.","metaTitle":"Schneider Electric A9N19643 DPN Vigi RCBO, Type A-SI, 13 A,","metaDescription":"Schneider Electric A9N19643 Acti9 DPN Vigi earth leakage circuit breaker. Type A-SI (Super Immunised), 13 A rated, 30 mA sensitivity, C-curve, 6 kA breaking capacity. Current produ","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Type":"Type A-SI (Super Immunised)","Range":"Acti9","Colour":"White","Standards":"EN/IEC 61009-1 EN/IEC 61009-2-1","Curve code":"C","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"DPN Vigi","Embedding depth":"72 mm","Tropicalisation":"2 conforming to EN 61009","lifecycle_stage":"current","Limitation class":"3 conforming to EN 61009","Local signalling":"ON/OFF indication","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3 conforming to EN 61009","Breaking capacity":"6000 A Icn at 230 V AC conforming to EN 61009","Device short name":"DPN N Vigi","Network frequency":"50/60 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Operating altitude":"2000 m","[In] rated current":"13 A at 30 °C","Overvoltage category":"III","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles conforming to IEC 61009","Mechanical durability":"20000 cycles","Connections - terminals":"Tunnel type terminals1 cable(s) 10 mm² flexible Tunnel type terminals1 cable(s) 16 mm² rigid","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"300 mA","Number of protected poles":"1","Product or component type":"Earth leakage circuit breaker","Contact position indicator":"Yes","Circuit breaker application":"Distribution","[Ui] rated insulation voltage":"400 V AC conforming to EN 61009","[Ue] rated operational voltage":"230 V AC 50/60 Hz","Ambient air temperature for storage":"-40...60 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"6000 A at 230 V AC 50/60 Hz conforming to EN 61009","[Uimp] rated impulse withstand voltage":"4 kV conforming to EN 61009"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/cda77606ecf73d1760b1c1db0cf72aa8.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9N19643/acti9-earth-leakage-circuit-breaker-dpn-n-vigi-1p-+-n-13a-300ma/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N19643/alternatives.json"},"ai":{"faq":[{"question":"What is A9N19643's listed type (Type A-SI (Super Immunised))?","answer":"The A9N19643 is a Type A-SI (Super Immunised) RCBO, meaning it is designed to resist nuisance tripping from high-frequency leakage currents generated by electronic loads like switched-mode power supplies and VFDs."},{"question":"How do I get current pricing and availability for A9N19643?","answer":"Submit an RFQ through this listing. Pricing and stock are confirmed at quote time through independent distribution channels — no automated price or stock count is displayed here."},{"question":"What compliance documentation does this brand provide for A9N19643?","answer":"The A9N19643 is certified to EN/IEC 61009-1 and EN/IEC 61009-2-1. It carries a pollution degree 3 rating and overvoltage category III per those standards. For RoHS/REACH declarations, refer to the manufacturer's documentation portal using the order code."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N19643","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N19643 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}