{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N19647","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N19647","canonicalUrl":"https://aoctrl.com/schneider/A9N19647","factsUrl":"https://aoctrl.com/api/mcp/products/A9N19647","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 DPN Vigi RCBO, Type A-SI (Super Immunised), 32A C-curve, 300mA earth leakage, 1P+N, 6kA breaking capacity.","salesMarkdown":"The Schneider Electric A9N19647 is an Acti9 DPN Vigi RCBO — a combined overcurrent and earth-leakage device in a single 1P+N module. The 32 A rated current (at 30 °C) and C-curve magnetic trip (5–10 × In) make it suitable for general-purpose distribution circuits feeding resistive and moderate inductive loads like lighting, small appliances, or control transformers. The 300 mA earth-leakage sensitivity is an equipment-protection level, not a personnel-protection level (that would be 30 mA or lower), so it is intended for circuits where nuisance tripping from leakage in long cable runs or industrial equipment needs to be avoided while still providing ground-fault protection. The 6 kA breaking capacity at 230 V AC conforming to EN 61009 covers most domestic and light commercial panel fault levels; if your available fault current exceeds that, you need an upstream current-limiting device. The Type A-SI (Super Immunised) designation means the residual current device (RCD) element is designed to resist unwanted tripping from high-frequency leakage currents generated by VFDs, UPS systems, or switching power supplies — a common headache in panels with non-linear loads. Standard Type A RCDs can nuisance-trip on those waveforms; the SI variant filters them out, so you get reliable earth-leakage detection without the false alarms. Tunnel-type terminals accept up to 16 mm² rigid or 10 mm² flexible cable, which is generous for a 32 A device and simplifies daisy-chaining in the panel. The toggle control gives a clear ON/OFF indication for local isolation. Ambient storage range is -40 to 60 °C, and it operates at altitudes up to 2000 m without derating.","metaTitle":"Schneider Electric A9N19647 Acti9 DPN Vigi, 32A C-Curve 30mA","metaDescription":"Schneider Electric A9N19647 Acti9 DPN Vigi RCBO, 32A C-curve, 300mA Type A-SI earth leakage. 6kA breaking capacity. DIN rail mount. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Type":"Type A-SI (Super Immunised)","Range":"Acti9","Colour":"White","Standards":"EN/IEC 61009-2-1 EN/IEC 61009-1","Curve code":"C","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"DPN Vigi","Embedding depth":"72 mm","Tropicalisation":"2 conforming to EN 61009","lifecycle_stage":"current","Limitation class":"3 conforming to EN 61009","Local signalling":"ON/OFF indication","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3 conforming to EN 61009","Breaking capacity":"6000 A Icn at 230 V AC conforming to EN 61009","Device short name":"DPN N Vigi","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Operating altitude":"2000 m","[In] rated current":"32 A at 30 °C","Overvoltage category":"III","Trip unit technology":"Thermal-magnetic","Electrical durability":"10000 cycles conforming to IEC 61009","Mechanical durability":"20000 cycles","Connections - terminals":"Tunnel type terminals1 cable(s) 10 mm² flexible Tunnel type terminals1 cable(s) 16 mm² rigid","Magnetic tripping limit":"5...10 x In","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"300 mA","Number of protected poles":"1","Product or component type":"Earth leakage circuit breaker","Contact position indicator":"Yes","Circuit breaker application":"Distribution","[Ui] rated insulation voltage":"400 V AC conforming to EN 61009","[Ue] rated operational voltage":"230 V AC","Ambient air temperature for storage":"-40...60 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"6000 A at 230 V AC 50/60 Hz conforming to EN 61009","[Uimp] rated impulse withstand voltage":"4 kV conforming to EN 61009"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2f109a1af398da66b082cbd1e3e72382.pdf","sourceUrl":"https://www.se.com/in/en/product/A9N19647/acti-9-earth-leakage-circuit-breaker-dpn-vigi-1p-+-n-32a-300ma/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N19647/alternatives.json"},"ai":{"faq":[{"question":"What is the difference between Type A and Type A-SI (Super Immunised)?","answer":"Type A-SI is a Type A RCD with enhanced immunity to high-frequency leakage currents from VFDs, UPS systems, and switching power supplies. It resists nuisance tripping on those waveforms while still detecting sinusoidal AC and pulsating DC fault currents."},{"question":"What standards does the A9N19647 comply with?","answer":"It complies with EN/IEC 61009-2-1 and EN/IEC 61009-1, which cover combined overcurrent and residual current devices for household and similar installations."},{"question":"Where can I buy the A9N19647 and get current pricing?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial response."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N19647","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N19647 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}