{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N19665","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N19665","canonicalUrl":"https://aoctrl.com/schneider/A9N19665","factsUrl":"https://aoctrl.com/api/mcp/products/A9N19665","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 DPN N Vigi RCBO, Type AC, 1P+N, 16 A, C curve, 30 mA earth leakage, 6 kA Icn at 230 V AC.","salesMarkdown":"It packs a thermal-magnetic trip for overload and short-circuit (C curve, magnetic trip 5–10 x In) plus voltage-independent residual current detection at 30 mA Type AC. That 30 mA sensitivity covers the standard personnel-protection threshold per EN/IEC 61009, so it's the go-to for socket-outlet circuits, lighting, and general-purpose final subcircuits where you need both fault-current and earth-leakage protection in one DIN-rail slot. The 30 mA residual sensitivity is instantaneous (no intentional delay), so it clears a ground fault in the time the standard requires — no coordination with downstream RCDs unless you add selective types upstream. Neutral is on the left, line on the right — fixed polarity, so verify busbar orientation before racking in. The toggle gives clear ON/OFF indication and a local contact-position flag.","metaTitle":"Schneider Electric A9N19665 DPN N Vigi RCBO, 16A C Curve 30m","metaDescription":"Schneider Electric A9N19665 DPN N Vigi RCBO, 16A rated, C curve, 30 mA Type AC residual current, 6 kA breaking capacity. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Color":"White","Voltage":"230 V AC","Control Type":"Toggle","Product Type":"Type AC","Product Status":"Active","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to EN 61009","Temp Storage Max":"60 °C","Temp Storage Min":"-40 °C","Breaking Capacity":"6000 A Icn at 230 V AC conforming to EN 61009","Insulation Voltage Ui":"400 V AC conforming to EN 61009","Temp Operating Max":"60 °C","Temp Operating Min":"-5 °C","Temperature Storage":"-40...60 °C","Electrical Life Cycles":"20000 cycles conforming to IEC 61009","Mechanical Life Cycles":"20000 cycles","Main Product Or Component Type":"Earth leakage circuit breaker","Ambient Air Temperature Operation":"-5...60 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/adb44fda2c900e9144b1e003619916e7.pdf","sourceUrl":"https://www.se.com/th/en/product/A9N19665/residual-current-breaker-with-overcurrent-protection-rcbo-acti9-dpn-n-vigi-1p+n-16a-30ma-ac-type-6000a/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N19665/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N19665","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N19665 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}