{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N19671","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N19671","canonicalUrl":"https://aoctrl.com/schneider/A9N19671","factsUrl":"https://aoctrl.com/api/mcp/products/A9N19671","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 DPN Vigi, earth leakage circuit breaker, Type AC, 1P+N, 6 A, B curve, 300 mA sensitivity, 6 kA Icn, DIN rail.","salesMarkdown":"The A9N19671: Type AC detection means this RCBO trips on sinusoidal AC earth-leakage currents only — the standard choice for general-purpose distribution circuits feeding resistive, inductive, or electronic loads without DC components or pulsed waveforms. It is not rated for Type A or Type F applications where smoothed DC or mixed-frequency leakage may be present. The 300 mA sensitivity is a fire-protection threshold, not a personnel-protection level (30 mA is typical for that). It suits outgoing sub-distribution circuits feeding fixed equipment where nuisance tripping from cable capacitance or surge suppressors would be a problem. B curve (3...5 x In) means the instantaneous magnetic trip operates between 18 A and 30 A for this 6 A unit. Rated insulation voltage 400 V AC and overvoltage category III confirm it is suitable for fixed-installation distribution boards downstream of the main incoming supply, not for final sub-circuits at the equipment level (category II). Neutral is on the left, phase on the right, which is the standard Acti9 DPN arrangement. Ambient operating temperature range is -25...60 °C (storage -40...60 °C), with 95% RH at 55 °C. Electrical and mechanical durability are both rated at 20,000 cycles per IEC 61009 — sufficient for distribution switching but not for frequent load-break duty like a contactor. The toggle actuator provides local ON/OFF indication.","metaTitle":"Schneider Electric A9N19671 DPN Vigi 6A Type AC RCBO, B Curv","metaDescription":"Schneider Electric A9N19671 Acti9 DPN Vigi RCBO. 6A rated, B curve, 300 mA Type AC earth leakage, 6 kA breaking capacity. DIN rail, current lifecycle. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Type":"Type AC","Range":"Acti9","Colour":"White","Standards":"EN/IEC 61009-2-1 EN/IEC 61009-1","Curve code":"B","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"DPN Vigi","Tropicalisation":"2 conforming to EN 61009","lifecycle_stage":"current","Limitation class":"3 conforming to EN 61009","Local signalling":"ON/OFF indication","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3 conforming to EN 61009","Breaking capacity":"6000 A Icn at 230 V AC 50/60 Hz conforming to EN 61009","Device short name":"DPN N Vigi","Network frequency":"50/60 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Operating altitude":"2000 m","[In] rated current":"6 A at 30 °C","Overvoltage category":"III","Trip unit technology":"Thermal-magnetic","Electrical durability":"20000 cycles conforming to IEC 61009","Mechanical durability":"20000 cycles","Connections - terminals":"Tunnel type terminals1 cable(s) 10 mm² flexible Tunnel type terminals1 cable(s) 16 mm² rigid","Magnetic tripping limit":"3...5 x In","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"300 mA","Number of protected poles":"1","Product or component type":"Earth leakage circuit breaker","Contact position indicator":"Yes","Circuit breaker application":"Distribution","[Ui] rated insulation voltage":"400 V AC conforming to EN 61009","[Ue] rated operational voltage":"230 V AC 50/60 Hz","Ambient air temperature for storage":"-40...60 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-5...60 °C","[Ics] rated service breaking capacity":"6000 A at 230 V AC 50/60 Hz conforming to EN 61009","[Uimp] rated impulse withstand voltage":"4 kV conforming to EN 61009"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f86b4f20314f2aceadd3354c21f53148.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9N19671/acti9-earth-leakage-circuit-breaker-dpn-n-vigi-1p-+-n-6a-300ma/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N19671/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9N19671 and how do I get a price?","answer":"The A9N19671 is sourced and quoted to order through independent distribution against an RFQ. Submit a request for quotation; availability and current pricing are confirmed at quote time."},{"question":"What is A9N19671's listed type (Type AC) on this component line?","answer":"The A9N19671 is listed as Type AC earth-leakage protection, meaning it detects sinusoidal AC residual currents only. It is not suitable for pulsed DC or smooth DC leakage."},{"question":"What is A9N19671's listed range (Acti9) on this component line?","answer":"The A9N19671 belongs to the Schneider Electric Acti9 range, a modular DIN-rail system for final distribution in residential and commercial buildings."},{"question":"What compliance documentation does this brand provide for A9N19671 (RoHS, REACH, UL, IEC)?","answer":"The A9N19671 is certified to EN/IEC 61009-1 and EN/IEC 61009-2-1. It carries CE marking for the European market. RoHS and REACH compliance documentation is available from the manufacturer upon request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N19671","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N19671 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}