{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9N19677","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9N19677","canonicalUrl":"https://aoctrl.com/schneider/A9N19677","factsUrl":"https://aoctrl.com/api/mcp/products/A9N19677","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 DPN N Vigi RCBO, A9N19677, 1P+N, 25 A, B-curve, 300 mA Type AC earth-leakage, 6 kA Icn, DIN-rail mount.","salesMarkdown":"The A9N19677 is a complete RCBO — overcurrent and earth-leakage protection in one 1P+N module. Rated 25 A at 30 °C with a B-curve magnetic trip (3...5 x In) and 300 mA Type AC residual current detection. Breaking capacity is 6 kA Icn at 230 V AC, 50/60 Hz, per EN/IEC 61009. No holes in the box — it ships ready for the DIN rail. The 300 mA sensitivity is a fire-protection level, not personnel protection (30 mA would be required for that). B-curve trips at 3–5x In, suited for resistive and lighting loads with modest inrush; if your circuit feeds motor or transformer loads, a C-curve would be the better call. ## Panel integration Neutral is fixed left, line right. Operating altitude is 2000 m; derate above that. Ambient storage range is -40 to 60 °C.","metaTitle":"Schneider Electric A9N19677 DPN N Vigi RCBO, 25A B-Curve 30m","metaDescription":"Schneider Electric A9N19677 Acti9 DPN N Vigi RCBO, 25A rated current, B-curve, 300mA Type AC earth-leakage protection, 6kA breaking capacity. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Type":"Type AC","Range":"Acti9","Colour":"White","Standards":"EN/IEC 61009-2-1 EN/IEC 61009-1","Curve code":"B","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"DPN Vigi","Tropicalisation":"2 conforming to EN 61009","lifecycle_stage":"current","Limitation class":"3 conforming to EN 61009","Local signalling":"ON/OFF indication","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3 conforming to EN 61009","Breaking capacity":"6000 A Icn at 230 V AC 50/60 Hz conforming to EN 61009","Device short name":"DPN N Vigi","Network frequency":"50/60 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Operating altitude":"2000 m","[In] rated current":"25 A at 30 °C","Overvoltage category":"III","Trip unit technology":"Thermal-magnetic","Electrical durability":"10000 cycles conforming to IEC 61009","Mechanical durability":"20000 cycles","Connections - terminals":"Tunnel type terminals1 cable(s) 10 mm² flexible Tunnel type terminals1 cable(s) 16 mm² rigid","Magnetic tripping limit":"3...5 x In","Earth-leakage protection":"Integrated","Device location in system":"Outgoer","Earth-leakage sensitivity":"300 mA","Number of protected poles":"1","Product or component type":"Earth leakage circuit breaker","Contact position indicator":"Yes","Circuit breaker application":"Distribution","[Ui] rated insulation voltage":"400 V AC conforming to EN 61009","[Ue] rated operational voltage":"230 V AC 50/60 Hz","Ambient air temperature for storage":"-40...60 °C","Earth-leakage protection time delay":"Instantaneous","Residual current tripping technology":"Voltage independent","Ambient air temperature for operation":"-5...60 °C","[Ics] rated service breaking capacity":"6000 A at 230 V AC 50/60 Hz conforming to EN 61009","[Uimp] rated impulse withstand voltage":"4 kV conforming to EN 61009"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2d17dca94cda575730addf6ec86eb0a8.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9N19677/acti9-earth-leakage-circuit-breaker-dpn-n-vigi-1p-+-n-25a-300ma/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9N19677/alternatives.json"},"ai":{"faq":[{"question":"What is A9N19677's Type AC detection?","answer":"Type AC means it detects sinusoidal AC residual currents only. It is the standard type for general distribution where no pulsed or smooth DC leakage is present."},{"question":"What is the breaking capacity of A9N19677?","answer":"6 kA Icn at 230 V AC, 50/60 Hz, conforming to EN/IEC 61009. Verify your prospective short-circuit current stays under this."},{"question":"Where can I buy A9N19677 and how is it quoted?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What compliance documentation does A9N19677 carry?","answer":"Certified to EN/IEC 61009-2-1 and EN/IEC 61009-1. Tropicalisation class 2 and limitation class 3 per EN 61009. Pollution degree 3."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9N19677","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9N19677 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}